Skip to main content
Schneider Electric VW3A4624 — AC Drive (VFD) 480V

Schneider VW3A4624 Passive Filter, 26 A, 400 V, 50 Hz, for A

MPNVW3A4624
Active

Schneider Altivar series, passive filter, VW3A4624, 26 A rated current, 400 V, 50 Hz, for variable speed drive harmonic reduction.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A4624 — Identification
ParameterValue
Product typePassive filter

Input / Supply

VW3A4624 — Input / Supply
ParameterValue
Rated supply voltage range400 V +/- 10 %
Network number of phases3 phases

Mechanical & Cooling

VW3A4624 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP20

Environmental

VW3A4624 — Environmental
ParameterValue
Operating ambient temperature40...55 °C (with current derating 3 % per °C) 5...40 °C (without current derating)
Operating altitude> 1000...4000 m with current derating 5 % per 1000 m
Relative humidity5...85 % without condensation
Storage / transport temperature-25...55 °C

Product details

What this filter does on the line

The VW3A4624 is a passive filter sized for Altivar drives in the 15 kW / 20 hp class — ATV61HD15N4, ATV61WD15N4, ATV71HD15N4, ATV71WD15N4, and the ATV61WD15N4C variant. It knocks line current harmonics down to 10 % THDI on the ATV61H and ATV71H motors, and further to 5 % THDI on the ATV61W motors. Rated at 26 A continuous, 400 V +/- 10 %, 50 Hz three-phase. The filter draws near-unity power factor — cos phi hits 0.99 at full load, 1.0 at 150 % line current, and 0.85 at light load (75 %). That's the power-factor correction working across the operating band, not just at one sweet spot. Efficiency is 98 %, so you lose about 2 % of the pass-through energy as heat. That's typical for a passive harmonic trap — the trade-off for not needing an active front end.

The terminal block accepts up to 50 mm² cable, which is generous for 26 A and tells you the filter is built for low voltage drop on the line side. One filter per drive; no daisy-chaining multiple drives off a single unit. Operating altitude derating kicks in above 1000 m: 5 % current reduction per additional 1000 m. If the panel sits at 3000 m, plan for roughly 10 % headroom on the 26 A rating. Relative humidity range is 5 to 85 % non-condensing.

Frequently asked questions

What THDI does VW3A4624 achieve?

The VW3A4624 delivers 10 % THDI when paired with ATV61H or ATV71H motors at 15 kW / 20 hp, and 5 % THDI with ATV61W motors at the same power rating.

What is the rated current and voltage for VW3A4624?

Rated current is 26 A at 400 V +/- 10 %, 50 Hz, three-phase. Maximum current is 1.5 times nominal (39 A peak).

Where can I buy VW3A4624?

The VW3A4624 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for VW3A4624?

The product carries an IP20 degree of protection and Class F electrical insulation. Standard Schneider documentation includes the product datasheet and installation manual. Specific RoHS, REACH, or UL declarations should be requested at quote time.

MPN
VW3A4624