Skip to main content
Schneider Electric VW3A5209 — Motor Control Accessories

Schneider Electric VW3A5209 Sinus Filter, 400 A, for Altivar

MPNVW3A5209
Active

Schneider Electric, Altivar series, Sinus filter, VW3A5209, 400 A rated current, 1900 W thermal losses at 100 Hz, IP00.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

VW3A5209 — Identification
ParameterValue
Product / component typeSinus filter
VW3A5209 — Electrical
ParameterValue
Rated current (In)400 A
VW3A5209 — Cable & Connector
ParameterValue
Electrical connectionBare wires diameter: 11 mm
VW3A5209 — Environmental
ParameterValue
IP protection ratingIP00
Operating ambient temperature40...50 °C (with current derating 1.5 % per °C) -10...40 °C (without current derating)
Storage ambient temperature-40...65 °C
Relative humidity0...95 %
Operating altitude1000...3000 m with current derating 1 % per 100 m
Environmental class3B1 conforming to IEC 721-3-3 3C2 conforming to IEC 721-3-3 3S1 conforming to IEC 721-3-3

Product details

What the 400 A Rating Means for Your Drive Line

The VW3A5209 is a sinus filter rated for 400 A continuous output current, designed for the output side of an Altivar variable speed drive. It cleans the PWM waveform from the drive into a near-sinusoidal voltage and current, which reduces motor heating, bearing currents, and reflected-wave spikes on long cable runs. The filter can handle 1.5 x nominal current for 60 seconds — useful for motor starting or short overload events.

Deployment Context — Panel and Environment

It connects via bare wires up to 11 mm diameter. Operating altitude up to 1000 m is full rating; above that, derate 1 % per 100 m up to 3000 m. Ambient temperature range is -10 to 40 °C without derating, and 40 to 50 °C with a 1.5 % per °C derating. Pollution degree 2 per EN 50178 covers normal industrial environments with only non-conductive contamination.

Vibration and Shock — What It Withstands

The filter is rated for vibration resistance of 1 gn (13–200 Hz) and 1.5 mm peak-to-peak (3–13 Hz) per IEC 60068-2. Shock resistance is 15 gn for 11 ms per IEC 60068-2-27. These ratings cover normal industrial panel vibration and occasional impact during transport or nearby equipment operation.

Frequently asked questions

What is VW3A5209's rated current and overload capability?

Rated continuous current is 400 A, with overload capability of 1.5 x nominal current for 60 seconds.

What thermal losses does VW3A5209 have at 100 Hz?

Thermal losses are 1900 W at 100 Hz output frequency.

Where can I buy VW3A5209?

The part is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What compliance documentation does Schneider provide for VW3A5209?

The filter is designed to EN 50178 (pollution degree 2) and tested to IEC 60068-2 for vibration and shock. Schneider typically provides CE declaration and RoHS/REACH data on request — confirm with your order.

MPN
VW3A5209