Skip to main content
Schneider Electric VW3A5216 — AC Drive (VFD) 600V

Schneider VW3A5216 Sinus Filter, 28 A, 690 V AC, UL 508

MPNVW3A5216
Active

Schneider Electric Altivar Process series, sinus filter, type VW3A5216, 28 A rated current, 690 V AC max voltage, UL 508 listed.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

VW3A5216 — Identification
ParameterValue
Product / component typeSinus filter
VW3A5216 — Output / Performance
ParameterValue
Switching (PWM) frequency2 kHz
VW3A5216 — Mechanical
ParameterValue
Terminal / wiring connectionTerminal
VW3A5216 — Environmental
ParameterValue
IP rating (with kit options)IP00
Operating ambient temperature-10...45 °C
Storage temperature-40...65 °C
Operating altitude (with derating)1000...3000 m with current derating 1 % per 100 m
Relative humidity0...95 %
Pollution degree2 conforming to EN 50178
Vibration resistance1 gn (f= 13...200 Hz) conforming to IEC 60068-2 1.5 mm peak to peak (f= 3...13 Hz) conforming to IEC 60068-2
Shock resistance15 gn for 11 ms conforming to IEC 60068-2-27
VW3A5216 — Approvals & Compliance
ParameterValue
StandardsUL 508

Product details

The VW3A5216 is a sinus output filter rated for 28 A continuous current, sized for Altivar Process variable speed drives. It cleans the PWM waveform from the drive output to a near-sinusoidal voltage, which reduces motor heating, eliminates reflected-wave stress on long cable runs, and quiets audible noise from the motor laminations. The 2 kHz switching frequency matches the typical IGBT carrier on many Altivar Process drives; if your drive runs a higher carrier, the filter still attenuates but derate the current per the drive's application note. The 70 Hz maximum output frequency means it suits standard induction motors up to 60 Hz base speed plus a small overspeed margin — not for high-speed spindle applications. UL 508 listing certifies it as an industrial control component for North American panels. The pollution degree 2 rating per EN 50178 means it's designed for normal factory-floor environments where only non-conductive dust settles — no condensation or conductive contamination expected.

Terminal electrical connection suits panel wiring with ring or fork terminals; no special connector tooling needed. Operating temperature range is -10 to 45 °C. Above 40 °C, the thermal losses of 280 W at 115 °C mean the panel must have adequate ventilation or forced cooling to keep the internal ambient below the limit. Storage range of -40 to 65 °C covers warehouse and shipping extremes. Altitude derating: rated at 1000 m; above that, derate current 1 % per 100 m up to 3000 m. At a 2000 m installation, that's a 10 % reduction — 25.2 A effective limit. Vibration resistance is 1 gn from 13 to 200 Hz, with 1.5 mm peak-to-peak from 3 to 13 Hz. Shock resistance is 15 gn for 11 ms. These are typical for panel-mounted industrial gear.

Overload and sourcing posture

The filter can handle 1.5 times nominal current for 60 seconds. This overload capability covers motor starting inrush and short-term process overloads without nuisance tripping or fuse coordination issues. For sustained overloads beyond 60 s, size up to the next filter rating.

Frequently asked questions

What are the key ratings for VW3A5216?

Rated current 28 A, maximum voltage 690 V AC, maximum output frequency 70 Hz, switching frequency 2 kHz, and UL 508 listed.

How do I get current pricing and availability for VW3A5216?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is the overload capability of VW3A5216?

It can handle 1.5 times nominal current for 60 seconds, covering motor starting inrush and short-term process overloads.

MPN
VW3A5216