Schneider Electric VW3A5407 — AC Drive (VFD) 480V

Schneider Electric VW3A5407 Sinus Filter, 305 A, 480 V AC

MPNVW3A5407
Active

Schneider Electric Altivar series, output sinus filter, VW3A5407, 305 A rated current, 480 V AC permissible voltage, IP00.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

VW3A5407 — Identification
ParameterValue
Product typeSinus filter

Mechanical & Cooling

VW3A5407 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00

Environmental

VW3A5407 — Environmental
ParameterValue
Operating ambient temperature50...60 °C (with current derating 1.5 % per °C) -15...50 °C (without current derating)
Operating altitude1000...4000 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation
Storage / transport temperature-40...70 °C
Pollution degree3 conforming to IEC 61800-5-1

Product details

What this filter does on the line

The VW3A5407 is an output sinus filter for Altivar variable-speed drives, sized for a 305 A continuous rating at 480 V AC. It converts the PWM output from the drive into a near-sinusoidal waveform, which means the motor sees cleaner voltage — less stress on the winding insulation and lower bearing currents. The filter is rated for a maximum output frequency of 100 Hz, so it covers standard induction motors and most high-speed spindle applications up to that limit. At 4 kHz switching frequency, the filter dissipates 676 W of thermal losses. That heat has to go somewhere — the IP00 enclosure means it's not sealed; it relies on free air or forced ventilation in the cabinet. Plan for that heat load in your panel thermal budget, especially if the filter shares an enclosure with other heat-generating gear.

Mounting and connection — what fits where

The filter measures 565 mm deep by 460 mm wide by 370 mm tall. That's a substantial footprint — verify the backplate or floor-mount area before committing the panel layout. Electrical connection is via M10 copper bars, accepting cable up to 300 mm² or 500 kcmil. That's a heavy lug; torque the M10 bolts to the manufacturer's spec for the bar material. Motor cable length can run up to 1000 m with unshielded cable, or 500 m with shielded. That range covers long conveyor lines or pump stations where the drive sits in a central MCC room and the motor is out on the plant floor. The IP00 rating means it's for indoor cabinet installation only — no washdown, no outdoor exposure.

Environmental and derating reality

The filter operates without derating from -15 °C to 50 °C ambient. Above 50 °C up to 60 °C, derate the current by 1.5 % per °C. At altitude above 1000 m up to 4000 m, derate 1 % per 100 m. The 3M4 shock and vibration class per IEC 60721-3-3 covers normal industrial transport and installation, not extreme mobile or marine environments. The filter also carries environmental resistance ratings: biological class 3B1, chemical class 3C3, and dust class 3S3 per IEC 60721-3-3. That 3C3 chemical rating is significant — it means the filter can handle moderate chemical exposure, like what you'd find in a wastewater treatment hall or a chemical dosing area, without the enclosure degrading.

Frequently asked questions

What are the key specifications for VW3A5407?

Rated 305 A continuous at 480 V AC, with a maximum output frequency of 100 Hz. Thermal losses are 676 W at 4 kHz switching frequency. Dimensions are 565 mm deep by 460 mm wide by 370 mm tall, with M10 copper bar connections accepting up to 300 mm² cable.

What compliance documentation does Schneider provide for VW3A5407?

The filter is designed to IEC 61800-5-1 (pollution degree 3) and IEC 60721-3-3 (mechanical and environmental classes). Standard Schneider documentation includes the datasheet and installation manual. For specific RoHS, REACH, or UL declarations, request them at quote time.

MPN