Skip to main content
Schneider Electric VW3A7263 — AC Drive (VFD) 600V

Schneider Electric VW3A7263 Line Filter Module, 220 kW, 500-

MPNVW3A7263
Obsolete

Schneider Electric Altivar VW3A7263 line filter module, 220 kW, 500-690 VAC, 185 A, IP00, built-in unit for Active Front End systems.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

VW3A7263 — Identification
ParameterValue
Device short name / model codeLFM
Product / component typeLine filter module
VW3A7263 — Electrical (input)
ParameterValue
Rated supply voltage500...690 V +/- 10 %
Network phases3 phases
Line (input) current185 A at 50 °C
VW3A7263 — Mechanical
ParameterValue
Terminal / wiring connectionBar M10 - 95 mm² 24 N.m (PE) Terminal - 2.5 mm² 0.6...0.8 N.m (X1:1...X1:6) Bar M10 - 185 mm² 24 N.m (1L1, 1L2, 1L3) Bar M10 - 185 mm² 24 N.m (2L1, 2L2, 2L3)
Product destination / compatibility1 active infeed converter (AIC) VW3A7270 1 active infeed converter (AIC) VW3A7271 1 active infeed converter (AIC) VW3A7272
VW3A7263 — Environmental
ParameterValue
IP rating (with kit options)IP00
Operating ambient temperature-10...45 °C -10...60 °C (with current derating of 2 % per °C)
Storage temperature-25...70 °C
Operating altitude (with derating)1000...2400 m with current derating 1 % per 100 m
Relative humidity0...95 %
Pollution degree2 conforming to EN/IEC 61800-5-1
Environmental resistance classes3K3 conforming to EN/IEC 60721-3-3 3C2 conforming to EN/IEC 60721-3-3 3S2 conforming to EN/IEC 60721-3-3
Vibration resistance1.5 mm (f= 3...10 Hz) conforming to IEC 60068-2-6 0.6 gn (f= 10...200 Hz) conforming to IEC 60068-2-6
Shock resistance7 gn for 11 ms conforming to EN/IEC 60068-2-27

Product details

The Schneider Electric VW3A7263 is a line filter module (LFM) rated for 220 kW at 500-690 VAC, designed as a component of the Active Front End (AFE) system for Altivar drives. It handles a line current of 185 A at 50 °C and dissipates 360 W of thermal losses via natural convection — no fan to fail, but the enclosure must allow free airflow around the 730 × 290 × 370 mm (H×W×D) built-in unit. This module is specifically intended for use with one active infeed converter (AIC) model VW3A7270, VW3A7271, or VW3A7272, and it also provides 24 VDC control electronics and fan power for the AIC plus up to four inverters of the same power class operating on 500-690 VAC.

The VW3A7263 is classified as Obsolete by Schneider Electric.

The 500-690 VAC ±10% supply voltage range covers standard 400 V-class and 690 V-class industrial networks in 50/60 Hz three-phase systems. The 185 A line current at 50 °C is the thermal limit under natural convection; above 45 °C ambient, derate the current by 2% per °C up to 60 °C. At altitudes above 1000 m, derate current 1% per 100 m to 2400 m max. Pollution degree 2 per EN/IEC 61800-5-1 is the standard for industrial control cabinets where non-conductive pollution occurs but occasional condensation is expected. Electrical connections use M10 bus bars for the power terminals (95 mm² for PE, 185 mm² for line) and a 2.5 mm² terminal for the control signals. Shock resistance is 7 gn for 11 ms per EN/IEC 60068-2-27, and vibration resistance is 1.5 mm at 3-10 Hz and 0.6 gn at 10-200 Hz per IEC 60068-2-6, which covers normal industrial machinery vibration.

Storage temperature range is -25 to 70 °C; operating range is -10 to 45 °C (with derating to 60 °C). Relative humidity tolerance is 0-95% non-condensing. Environmental classification per EN/IEC 60721-3-3 is 3K3 (temperature and humidity), 3C2 (chemical gases), and 3S2 (mechanical particles) — suitable for most factory-floor conditions without aggressive atmospheres.

Frequently asked questions

What are the physical dimensions of VW3A7263?

The VW3A7263 measures 730 mm high, 290 mm wide, and 370 mm deep (H×W×D). It is a built-in unit with IP00 protection.

What compliance documentation does this brand provide for VW3A7263?

The module carries pollution degree 2 certification per EN/IEC 61800-5-1 and environmental classification per EN/IEC 60721-3-3. Shock and vibration testing follows EN/IEC 60068-2-27 and IEC 60068-2-6 respectively. Specific RoHS, REACH, or UL documentation should be confirmed at time of order.

MPN