Schneider Electric VW3A7263
MPNVW3A7263
Obsolete
line filter module - 220 kW - 500...690 V
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Device short name / model code | LFM |
| Product / component type | Line filter module |
Electrical (input)
| Parameter | Value |
|---|---|
| Rated supply voltage | 500...690 V +/- 10 % |
| Network phases | 3 phases |
| Line (input) current | 185 A at 50 °C |
Mechanical
| Parameter | Value |
|---|---|
| Terminal / wiring connection | Bar M10 - 95 mm² 24 N.m (PE) Terminal - 2.5 mm² 0.6...0.8 N.m (X1:1...X1:6) Bar M10 - 185 mm² 24 N.m (1L1, 1L2, 1L3) Bar M10 - 185 mm² 24 N.m (2L1, 2L2, 2L3) |
| Product destination / compatibility | 1 active infeed converter (AIC) VW3A7270 1 active infeed converter (AIC) VW3A7271 1 active infeed converter (AIC) VW3A7272 |
Environmental
| Parameter | Value |
|---|---|
| IP rating (with kit options) | IP00 |
| Operating ambient temperature | -10...45 °C -10...60 °C (with current derating of 2 % per °C) |
| Storage temperature | -25...70 °C |
| Operating altitude (with derating) | 1000...2400 m with current derating 1 % per 100 m |
| Relative humidity | 0...95 % |
| Pollution degree | 2 conforming to EN/IEC 61800-5-1 |
| Environmental resistance classes | 3K3 conforming to EN/IEC 60721-3-3 3C2 conforming to EN/IEC 60721-3-3 3S2 conforming to EN/IEC 60721-3-3 |
| Vibration resistance | 1.5 mm (f= 3...10 Hz) conforming to IEC 60068-2-6 0.6 gn (f= 10...200 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 7 gn for 11 ms conforming to EN/IEC 60068-2-27 |
MPN
VW3A7263