Skip to main content
Schneider Electric VW3A7266 — Motor Control Accessories

Schneider VW3A7266 Line Filter Choke, 255 A, 380-480 V, Obso

MPNVW3A7266
Obsolete

Schneider Electric VW3A7266 line filter choke, 175 kW, 380-480 V, 255 A at 50 °C, IP00, built-in unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

VW3A7266 — Identification
ParameterValue
Product / component typeLine filter choke
VW3A7266 — Electrical
ParameterValue
Network frequency50/60 Hz
VW3A7266 — Cable & Connector
ParameterValue
Electrical connectionBar M10 - 2 x 150 mm² 24 N.m (1) Bar M10 - 2 x 150 mm² 24 N.m (2) Bar M10 - 95 mm² 24 N.m (PE)
VW3A7266 — Mechanical
ParameterValue
Width835 mm
Height295 mm
Depth195 mm
VW3A7266 — Environmental
ParameterValue
IP protection ratingIP00
Operating ambient temperature-10...45 °C -10...60 °C (with current derating)
Storage ambient temperature-25...70 °C
Relative humidity0...95 %
Operating altitude1000...3000 m with current derating 1 % per 100 m
Environmental class3K3 conforming to EN/IEC 60721-3-3

Product details

Line filter choke for Active Front End — now obsolete

The VW3A7266 is a line filter choke (LFC) designed for Schneider's Active Front End (AFE) system, specifically mating with the VW3A7251 and VW3A7252 active infeed converters. It's rated for 255 A line current at 50 °C on a 380-480 V three-phase network, dissipating 1275 W of thermal losses through natural convection cooling — no fan required. The part is now classified as obsolete per the manufacturer's lifecycle status.

The 255 A at 50 °C is the continuous current rating before derating — not a surge or peak figure. Above 50 °C ambient, the operating range extends to 60 °C with current derating applied. At altitude above 1000 m, derate 1 % per 100 m up to 3000 m. The 1275 W heat load is significant for panel thermal design: natural convection means you need free air movement around the 835 mm wide × 295 mm high × 195 mm deep chassis. IP00 means no enclosure protection — it's a built-in unit for a cabinet, not a standalone floor mount.

Mechanical and environmental integration

Electrical connection uses M10 bars: two runs of 2 × 150 mm² per phase plus a 95 mm² PE bar, torqued to 24 N·m. The built-in assembly style means it's designed to be bolted into a cabinet backplate — no DIN-rail mounting. Vibration resistance is 1.5 mm at 3-10 Hz and 0.6 gn at 10-200 Hz per IEC 60068-2-6; shock resistance is 7 gn for 11 ms per EN/IEC 60068-2-27. Storage temperature range is -25 to 70 °C; operating range is -10 to 45 °C (or 60 °C with derating). Insulation is Class H, suitable for the high thermal stress of a 1275 W choke running at line current.

Frequently asked questions

What is the line current rating of VW3A7266?

The VW3A7266 is rated for 255 A line current at 50 °C ambient. Above 50 °C, derating applies up to 60 °C. At altitudes above 1000 m, derate 1 % per 100 m.

What are the physical dimensions of VW3A7266?

The VW3A7266 measures 835 mm wide × 295 mm high × 195 mm deep. It is a built-in unit with IP00 protection, designed for cabinet mounting.

Where can I buy VW3A7266?

As an obsolete part, VW3A7266 is sourced through independent industrial automation distributors. Submit an RFQ for current availability and pricing — the part is quoted to order, not stocked on the shelf.

MPN
VW3A7266