Skip to main content
Schneider Electric WB1EA024 — Reversing Contactors

Schneider TeSys WB1EA024 Contactor Coil, 24 V AC, Obsolete

MPNWB1EA024
Obsolete

Schneider TeSys WB1EA024 contactor coil, 24 V AC 50 Hz, low consumption type, for CV1B and CV3B contactors.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

WB1EA024 — Identification
ParameterValue
Product rangeTeSys
Product or component typeContactor coil
WB1EA024 — Electrical
ParameterValue
Control circuit voltage [Uc]24 V AC 50 Hz
Control circuit typeAC
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at <131 °F (55 °C))
Inrush power220...270 VA 50 Hz 0.4 68 °F (20 °C))
Hold-in power consumption35...55 VA 50 Hz 0.35 68 °F (20 °C))
WB1EA024 — Other specifications
ParameterValue
Coil typeLow consumption
Inrush power in90...110 W 68 °F (20 °C)
Average resistance0.5 Ohm 68 °F (20 °C)
Inductance of closed circuit0.038 H
Hold-in power consumption in13...19 W 68 °F (20 °C)

Product details

The Schneider TeSys WB1EA024 is a replacement contactor coil, 24 V AC 50 Hz, designed for the CV1B and CV3B contactors in the TeSys range. It is a low-consumption coil type: inrush power draw is 90 to 110 W (220 to 270 VA at 50 Hz, 0.4 power factor), and hold-in consumption drops to 13 to 19 W (35 to 55 VA at 50 Hz, 0.35 power factor). Average resistance is 0.5 ohm, and closed-circuit inductance is 0.038 H. Control voltage limits are 0.85 to 1.1 times Uc at 50 Hz, operational up to 55 °C ambient.

This coil mounts directly onto the contactor magnet assembly of CV1B and CV3B frames. The 24 V AC 50 Hz control circuit is typical for panel applications where a control transformer supplies the coil bus. The low-consumption design keeps heat dissipation in the panel manageable — hold-in power under 20 W means the coil contributes minimal temperature rise inside the enclosure.

Frequently asked questions

What is the closest alternative to WB1EA024?

No official direct successor order code is published. A current-production TeSys coil with the same 24 V AC rating and mounting for CV1B/CV3B frames should be evaluated as a functional replacement, but pin compatibility and electrical characteristics must be verified against the specific contactor variant.

How can I source WB1EA024 if it is obsolete?

Submit an RFQ. We can search surplus and independent-channel inventory for available units. No stock count or lead time can be guaranteed without a live quote.

MPN
WB1EA024