Skip to main content
Schneider Electric WB1EA455 — Reversing Contactors

Schneider Electric WB1EA455 TeSys Contactor Coil, 440-500 V

MPNWB1EA455
Obsolete

Schneider Electric TeSys range, contactor coil WB1EA455, 440 V AC / 500 V AC control circuit, low-consumption coil for CV1B/CV3B contactors.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

WB1EA455 specifications
ParameterValue
Coil typeLow consumption
Control circuit typeAC
Product or component typeContactor coil
Coil voltage440 V AC 50 Hz 450 V AC 50 Hz 500 V AC 60 Hz
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 60 Hz (at <131 °F (55 °C))
Inrush power in90...110 W 68 °F (20 °C) 75...95 W 68 °F (20 °C)
Hold-in power consumption in13...19 W 68 °F (20 °C) 10...13 W 68 °F (20 °C)
RangeTeSys
Category18402-WORLD SERVICE PARTS(CONTROL ACCESS)
Average resistance233 Ohm 68 °F (20 °C)
Inductance of closed circuit14 H

Product details

The Schneider Electric WB1EA455 is a low-consumption contactor coil from the TeSys range, designed to replace the coil in CV1B and CV3B contactors. It operates on a 440 V AC at 50 Hz or 500 V AC at 60 Hz control circuit, drawing an inrush of 220...270 VA at 50 Hz and holding at 35...55 VA.

The coil's average resistance is 233 ohms at 20 °C, which determines the steady-state current draw in the hold-in phase. Inrush power sits at 90...110 W (75...95 W at 20 °C), while hold-in power drops to 13...19 W (10...13 W at 20 °C). These figures matter for sizing the control transformer and verifying the contactor's pick-up voltage under load — the operational voltage limits are 0.85 to 1.1 Uc at 50/60 Hz below 55 °C.

Deployment context

This coil mounts into the CV1B or CV3B contactor frame, which is typically installed in motor control panels or general switching assemblies on a DIN rail or backplate. The low-consumption coil design reduces heat buildup in the enclosure, which helps when multiple contactors are ganged in a confined panel.

Frequently asked questions

What contactors does the WB1EA455 fit?

It is the replacement coil for Schneider Electric CV1B and CV3B contactors within the TeSys range.

What is the control voltage for this coil?

The coil accepts 440 V AC at 50 Hz or 500 V AC at 60 Hz. Operational limits are 0.85 to 1.1 Uc at those frequencies below 55 °C.

How do I source this obsolete part?

Since it is obsolete, new-stock availability is limited to surplus inventory. Submit an RFQ to confirm current stock position and pricing — no standard lead time applies.

MPN
WB1EA455