Skip to main content
Schneider Electric WB1EA970

WB1EA970 TeSys Contactor Coil, 500V AC / 400V DC, Obsolete

MPN WB1EA970
Obsolete

Schneider Electric TeSys contactor coil WB1EA970, 500V AC 50-400Hz & 400V DC, low-consumption, for CV1B/CV3B contactors, obsolete.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

WB1EA970 specifications
ParameterValue
Coil typeLow consumption
Control circuit typeDC AC
Main product or component typeContactor coil
Coil voltage500 V AC 50...400 Hz 400 V DC
Mechanical life cycles1200000 cycles
Operating time9 ms sealed

Product details

The Schneider Electric WB1EA970 is a low-consumption contactor coil in the TeSys range. It accepts dual control voltage: 500 V AC at 50-400 Hz or 400 V DC. Rated mechanical durability of 1,200,000 cycles and a maximum operating rate of 120 cycles per minute at 55 °C — this coil is built for sustained high-speed switching in production lines, not just occasional isolation duty.

Schneider has marked the WB1EA970 as obsolete.

Inrush power draw of 70-150 W (85-180 VA) at 20 °C, dropping to just 0.25-0.7 W hold-in consumption — that low hold power is the whole point of the low-consumption design, keeping the coil cool in a crowded DIN-rail enclosure and reducing the demand on the control transformer. Sealed operating time of 9 ms means the contacts close fast enough for most motor-starting and switching sequences, but the buyer should verify the pick-up time matches the PLC scan cycle or safety relay timing in their specific circuit. Coil resistance averages 1374.5 ohms at 20 °C — useful for calculating inrush current or verifying the coil is intact with an ohmmeter during troubleshooting.