Skip to main content
Schneider Electric WB1GA085 — Reversing Contactors

Schneider TeSys WB1GA085 Contactor Coil, 85 V DC, Obsolete

MPNWB1GA085
Obsolete

Schneider Electric TeSys WB1GA085, contactor coil, AC/DC operated, 85 V DC, low consumption, for CV1B and CV3B contactors.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

WB1GA085 — Identification
ParameterValue
Product rangeTeSys
Product or component typeContactor coil
WB1GA085 — Electrical
ParameterValue
Control circuit voltage [Uc]85 V DC
Control circuit typeAC/DC
WB1GA085 — Other specifications
ParameterValue
Coil typeLow consumption
Inrush power in130...250 W 68 °F (20 °C) 2P
Average resistance4.17 Ohm 68 °F (20 °C)
Maximum operating rate7200 cyc/mn 131 °F (55 °C)

Product details

The Schneider Electric TeSys WB1GA085 is a low-consumption contactor coil, AC/DC operated, rated for 85 V DC control voltage. It is designed as a service part for the CV1B and CV3B contactor frames within the TeSys range. The coil draws an inrush power of 130 to 250 W at 68 °F (20 °C) and has an average resistance of 4.17 Ohm at the same temperature. Its maximum operating rate is 7200 cycles per minute at 131 °F (55 °C).

For a BOM line requiring this exact coil, the procurement path is a cross-reference search against the CV1B/CV3B contactor frame specifications, or sourcing the WB1GA085 from the independent market.

The 85 V DC control voltage is the critical fit parameter — this coil will not pull in on a 24 V DC or 110 V AC control circuit. Verify your panel's control voltage matches before specifying. The low-consumption coil type means reduced heat dissipation in the enclosure, which matters when multiple contactors are ganged in a small panel. The 7200 cycles/minute maximum operating rate at 55 °C is a mechanical limit for the coil's plunger and armature, not an electrical switching rate. For high-speed applications like motor reversing or capacitor bank switching, confirm your duty cycle stays under this ceiling.

Frequently asked questions

What contactors does the WB1GA085 fit?

It is designed for the Schneider Electric TeSys CV1B and CV3B contactor frames.

What is the control voltage for this coil?

85 V DC, AC/DC operated.

What is the inrush power of this coil?

130 to 250 W at 68 °F (20 °C).

MPN
WB1GA085