Skip to main content
Schneider Electric WB1GA400 — Reversing Contactors

Schneider TeSys WB1GA400 Contactor Coil, 400-450V AC

MPNWB1GA400
Obsolete

Schneider TeSys series, contactor coil, WB1GA400, 400-450V AC 50/60Hz, low consumption type.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

WB1GA400 — Identification
ParameterValue
Product rangeTeSys
Product or component typeContactor coil
WB1GA400 — Electrical
ParameterValue
Control circuit voltage [Uc]440 V AC 60 Hz 450 V AC 60 Hz 400 V AC 50 Hz
Control circuit typeAC
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at Operational: 0.85...1.1 Uc at 60 Hz (at <131 °F (55 °C))
Inrush power345...415 VA 50 Hz 0.38 68 °F (20 °C)) 370...475 VA 60 Hz 0.35 68 °F (20 °C))
Hold-in power consumption45...65 VA 50 Hz 0.35 68 °F (20 °C)) 50...75 VA 60 Hz 0.37 68 °F (20 °C))
WB1GA400 — Other specifications
ParameterValue
Coil typeLow consumption
Inrush power in130...160 W 68 °F (20 °C) 130...165 W 68 °F (20 °C)
Average resistance110.71 Ohm 68 °F (20 °C)
Inductance of closed circuit7.3 H
Hold-in power consumption in16...25 W 68 °F (20 °C) 19...30 W 68 °F (20 °C)

Product details

The Schneider TeSys WB1GA400 is a replacement contactor coil, designed for the CV1B and CV3B contactor frames. It's a low-consumption AC coil rated for 400 V AC at 50 Hz and 440 to 450 V AC at 60 Hz. Control circuit voltage limits are 0.85 to 1.1 Uc at 50 and 60 Hz, up to 55 °C. Inrush power runs 130 to 165 W and 345 to 475 VA depending on frequency and temperature; hold-in drops to 16 to 30 W and 45 to 75 VA. The closed-circuit inductance is 7.3 H, with an average DC resistance of 110.71 ohms at 20 °C.

This part is obsolete per Schneider's lifecycle status.

What to watch when swapping

The coil is AC control circuit only. It's a service part for the CV1B and CV3B contactors. If you're replacing a failed coil on an existing panel, verify the contactor frame matches. If the contactor itself is also obsolete, a complete contactor replacement may be the faster path.

Frequently asked questions

What contactors does the WB1GA400 fit?

It is designed for the Schneider CV1B and CV3B contactor frames, as a replacement coil.

What is the control voltage for this coil?

It accepts 400 V AC at 50 Hz, and 440 V AC or 450 V AC at 60 Hz. The control circuit is AC only.

How do I source an obsolete WB1GA400?

Since it's obsolete, procurement is through the surplus and broker market. Submit an RFQ and we can locate available inventory from our sourcing network.

MPN