Specifications

WB1HA480 — Identification
ParameterValue
Product rangeTeSys
Product or component typeContactor coil
WB1HA480 — Electrical
ParameterValue
Control circuit voltage [Uc]450 V AC 50 Hz
Control circuit typeAC
Control circuit voltage limitsOperational: 0.85...1.1 Uc at 50 Hz (at <131 °F (55 °C))
Inrush power500...615 VA 50 Hz 0.31 68 °F (20 °C))
Hold-in power consumption60...85 VA 50 Hz 0.38 68 °F (20 °C))
WB1HA480 — Other specifications
ParameterValue
Coil typeLow consumption
Inrush power in155...190 W 68 °F (20 °C)
Average resistance86.03 Ohm 68 °F (20 °C)
Inductance of closed circuit8.5 H
Hold-in power consumption in22...35 W 68 °F (20 °C)

Product details

The WB1HA480 is a low-consumption contactor coil from the Schneider Electric TeSys range, designed for use with CV1B and CV3B contactors. It operates on a 450 V AC 50 Hz control circuit, drawing an inrush power of 155...190 W (500...615 VA at 50 Hz) and holding in at 22...35 W (60...85 VA at 50 Hz). The coil resistance is 86.03 Ω at 68 °F (20 °C), with a closed-circuit inductance of 8.5 H.

Control circuit voltage and operating limits

Rated for 450 V AC at 50 Hz, the coil's operational voltage limits are 0.85...1.1 Uc at 50 Hz, up to 131 °F (55 °C).

Power consumption profile

The inrush-to-hold power ratio is notable: 155...190 W inrush drops to 22...35 W sealed. In VA terms, the inrush spike of 500...615 VA collapses to 60...85 VA holding. This low-hold design reduces thermal buildup inside the contactor enclosure and lowers the burden on control transformers — relevant when multiple coils share a single control supply. The 0.31 power factor at inrush (0.38 holding) confirms a largely inductive load, so any auxiliary contact suppression or snubber should be rated for AC inductive switching.

Frequently asked questions

What contactors does the WB1HA480 coil fit?

This coil is designed for Schneider Electric CV1B and CV3B contactors from the TeSys range. It is a direct replacement coil for those specific frame sizes.

What is the power consumption of the WB1HA480?

Inrush power is 155...190 W (500...615 VA at 50 Hz, power factor 0.31). Holding power drops to 22...35 W (60...85 VA at 50 Hz, power factor 0.38). Coil resistance is 86.03 Ω at 68 °F (20 °C).

MPN