Rated for AC-3 duty at 500 V it handles 4.5 kW, and at 690 V it handles 5.5 kW — so it's sized for small-to-medium induction motors on 400 V to 690 V three-phase supplies. Auxiliary contact ratings span 10 A at 24 V down to 0.3 A at 220 V, covering control circuit loads across common DC and AC voltages.
Termination and wiring notes
Both main and auxiliary circuits use screw-type terminals. The main contacts accept 2x (0.5 to 1.5 mm²), 2x (0.75 to 2.5 mm²), or max 2x (0.75 to 4 mm²) solid/stranded, with AWG equivalents of 2x (20-16), 2x (18-14), or 1x 12. Auxiliary contacts share the same wire range. Degree of pollution is 3, so it's rated for conductive environments inside the enclosure. Side-by-side mounting is allowed without derating, which is typical for the S00 frame.