SIRIUS size S00 power contactor — 45 mm, screw terminals, 24 VDC coil
It carries an auxiliary switch and is rated for 10 A at 24 V, 3 A at 400 V, and 1 hp at 230 V. Mechanical life is typical 30,000,000 operations.
DIN rail fit and panel clearances
Dimensions: 73 mm deep, 58 mm high. Wire range: solid or stranded 0.5 to 4 mm², with multi-conductor capability up to 2x 4 mm².
Switching rates and arcing time
Maximum switching rates: 1,000 1/h at AC-1, 750 1/h at AC-2, 750 1/h at AC-3, 750 1/h at AC-3e, and 250 1/h at AC-4.
Auxiliary switch rated for 10 A at 24 V, 2 A at 48 V, 2 A at 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, and 0.2 A at 440 V. Main contact range: 20 to 12.