Skip to main content
Siemens 3RT2016-1AP01-ZX95 — Contactors

Siemens 3RT2016-1AP01-ZX95 SIRIUS Power Contactor, Size S00,

MPN3RT2016-1AP01-ZX95
Active

Siemens SIRIUS power contactor, size S00, 24 VDC coil, screw-type terminals, 10 A auxiliary contact rating at 24 V, 45 mm width, 73 mm depth, 58 mm height.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3RT2016-1AP01-ZX95 — Identification
ParameterValue
Contactor frame sizeS00
3RT2016-1AP01-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V8.5 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V1 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2016-1AP01-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC
Rated value @ 50 Hz0.25
Rated value @ 50 Hz230 V
3RT2016-1AP01-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2016-1AP01-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 35A (690V,100kA), aM: 20A (690V,100kA), BS88: 35A (415V,80kA)
Short-circuit coordination type 2, fusegG: 20A (690V,100kA), aM: 16A (690V, 100kA), BS88: 20A (415V, 80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2016-1AP01-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionscrew-type terminals
Conductor cross-section, solid0.5 ... 4 mm²
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 60715
Side-by-side mountingYes
3RT2016-1AP01-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)30 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2016-1AP01-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2016-1AP01-ZX95 — Mechanical
ParameterValue
Width45 mm
Height58 mm
Depth73 mm
3RT2016-1AP01-ZX95 — Specifications
ParameterValue
At AC7 ... 13 ms

Product details

It mounts via screw or snap-on onto a 35 mm DIN rail per DIN EN 60715, and the mounting position allows ±180° rotation on a vertical surface plus ±22.5° tilt forward/backward, giving flexibility in tight enclosures. The coil is 24 VDC with screw-type terminals, and the contactor carries an auxiliary switch block. The auxiliary contacts are rated at 10 A at 24 V, 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, 0.3 A at 220 V, 3 A at 400 V, and 0.2 A at 440 V — these are the maximum resistive (AC-1) or general-use ratings, so for inductive loads like contactor coils or small relays, derate accordingly.

Switching Frequency and Duty Cycle

The contactor's maximum switching rate depends on the duty category: 1,000 operations per hour for AC-1 (resistive), 750 ops/h for AC-2 and AC-3 (motor starting/running), and 250 ops/h for AC-4 (plugging/inching). The AC-3e rating also caps at 750 ops/h. These limits reflect the thermal recovery time of the arc chamber — exceeding them shortens contact life or causes welding.

Wiring and Environmental Limits

Main and auxiliary terminals accept solid or stranded wire from 0.5 to 4 mm², with dual-wire capability: 2×(0.5–1.5 mm²), 2×(0.75–2.5 mm²), or 2×4 mm². The contactor's dimensions — 45 mm wide, 58 mm high, 73 mm deep — fit standard 45 mm modular spacing, and the 10 mm clearance above/below/side is typical for heat dissipation and arc venting.

Frequently asked questions

What is the closest functional second-source — 3RT2026-1AG20?

The 3RT2026-1AG20 is a different S00 contactor; it shares the same frame size and DIN-rail mounting but may have a different coil voltage or auxiliary contact configuration. Verify coil voltage and auxiliary ratings before substituting.

What is the listed depth of this contactor?

The depth is 73 mm.

What wire sizes does it accept?

Solid or stranded wire from 0.5 to 4 mm², with dual-wire capability up to 2×4 mm².

Will it drop into a panel specified around 3RT2026-1AG20 without rewiring?

Mechanically yes — same S00 frame and DIN-rail clip. Electrically, confirm the coil voltage (24 VDC for this part) and that the auxiliary contact ratings match your control circuit.

What compliance documentation is available?

The evidence does not list specific certifications (UL, CSA, CE, RoHS, REACH). For a definitive compliance statement, request documentation with your RFQ.

MPN
3RT2016-1AP01-ZX95