Skip to main content
Siemens 3RT2036-1NB30-ZX95 — Contactors

Siemens 3RT2036-1NB30-ZX95 SIRIUS Power Contactor, S2, 20-33

MPN3RT2036-1NB30-ZX95

Siemens SIRIUS power contactor, S2 frame, 3RT2036-1NB30-ZX95, 20-33 V coil, screw-type terminals, auxiliary switch included, 55 x 114 x 130 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3RT2036-1NB30-ZX95 — Identification
ParameterValue
Contactor frame sizeS2
3RT2036-1NB30-ZX95 — Ratings & Performance
ParameterValue
Rated operational current, AC-12, max.10 A
Rated operational current, AC-4 @ 400 V41 A
Rated value @ 400 V3 A
Rated value @ 500 V2 A
Rated value @ 690 V1 A
Rated value @ 230 V10 hp
Rated value @ 24 V10 A
Rated value @ 60 V2 A
Rated value @ 110 V1 A
Rated value @ 220 V0.3 A
3RT2036-1NB30-ZX95 — Control & Coil
ParameterValue
Control supply voltage typeAC/DC
Rated value @ 50 Hz2 VA
Rated value @ 50 Hz20 ... 33 V
3RT2036-1NB30-ZX95 — Contacts & Poles
ParameterValue
Main poles3
Main NO contacts3
Auxiliary contact reliability1 faulty switching per 100 million (17 V, 1 mA)
3RT2036-1NB30-ZX95 — Protection & Coordination
ParameterValue
Short-circuit coordination type 1, fusegG: 160 A (690 V, 100 kA), aM: 80 A (690 V, 100 kA), BS88: 125 A (415 V, 80 kA)
Short-circuit coordination type 2, fusegG: 80A (690V,100kA), aM: 50A (690V,100kA), BS88: 63A (415V,80kA)
Aux. switch short-circuit protection, fusegG: 10 A (500 V, 1 kA)
3RT2036-1NB30-ZX95 — Connection & Mounting
ParameterValue
Main circuit connectionscrew-type terminals
Aux. / control circuit connectionspring-loaded terminals
Conductor cross-section, solid or stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded w/ ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Side-by-side mountingYes
3RT2036-1NB30-ZX95 — Durability
ParameterValue
Durability (operating cycles, typ.)10 000 000
Durability with aux. switch block (cycles, typ.)10 000 000
3RT2036-1NB30-ZX95 — Environmental
ParameterValue
Operating temperature range-25 ... +60 °C
Storage temperature range-55 ... +80 °C
Installation altitude, max.2 000 m
3RT2036-1NB30-ZX95 — Mechanical
ParameterValue
Width55 mm
Height114 mm
Depth130 mm
3RT2036-1NB30-ZX95 — Specifications
ParameterValue
At AC30 ... 55 ms

Product details

It mounts via screw or snap-on onto 35 mm DIN rail per DIN EN 60715, with a mounting position that allows +/-180° rotation on a vertical surface and +/-22.5° forward/backward tilt. Envelope dimensions are 55 mm wide, 114 mm high, and 130 mm deep — the depth is the dimension that typically drives cabinet depth when panel-mounted.

Coil and auxiliary contact ratings

Auxiliary contacts are rated for 10 A at 24 V, stepping down to 2 A at 48 V and 60 V, 1 A at 110 V, 0.9 A at 125 V, and 0.3 A at 220 V — these are the DC switching limits for the built-in auxiliary switch block.

Switching frequency and endurance

Maximum switching frequency varies by duty: 1,000 operations per hour at AC-1, 600 at AC-2, 800 at AC-3 and AC-3e, and 250 at AC-4.

Environmental and wiring

Main contact terminals accept 2x (0.5-1.5 mm²) or 2x (0.75-2.5 mm²) solid or stranded wire.

Frequently asked questions

What coil voltage does this contactor use?

Rated coil voltage range is 20-33 V, with screw-type terminals on the magnet coil.

Will 3RT2036-1NB30-ZX95 drop into a panel specified around 3RT2015-1BW42?

The 3RT2036 is an S2 frame size, while the 3RT2015 is a smaller S0 frame — physical dimensions differ, so it will not directly swap without panel rework.