It measures 140 mm high, 70 mm wide, and 152 mm deep — a compact footprint for a size S3 frame, leaving room for auxiliary contact blocks (two attachable) and wiring clearance of 10 mm upwards, 10 mm downwards, 20 mm forwards, and 10 mm at the side. The main power terminals accept stranded conductors from 6 mm² up to 70 mm², while the coil and auxiliary terminals handle solid or stranded wire from 0.5 mm² to 2.5 mm².
Rated operational current for AC-1 duty at 690 V is 1 A; at 400 V it is 3 A; at 230 V it is 6 A — these are the resistive-load curves. For inductive loads at lower voltages, the contactor is rated 10 A at 24 V, 2 A at 48 V, and 2 A at 60 V. Coil draws 0.35 A at 50 Hz and 0.41 A at 60 Hz, both at 230 V — a standard AC coil draw that fits typical control transformer sizing.