The Trip Class 10 rating means it will trip within 10 seconds at 7.2× the thermal setting, matching the startup profile of standard induction motors.
The 45 mm width and 97 mm depth fit standard panel layouts — no extra side clearance needed forward or backward (0 mm each way), though 50 mm above and below is required for ventilation and wiring access. Spring-loaded terminals on the main circuit accept 2× (0.5 to 4 mm²) solid or stranded wire, so no lug crimping for typical motor branch circuits.