Rated Trip Class 10, it clears overloads within 10 seconds at 7.2× setting current — the standard for protecting standard induction motors against locked-rotor conditions without nuisance tripping during normal starts. Breaking capacity reaches 100 kA at 400 V AC and 690 V AC, providing high fault-current interruption capability that supports selective coordination downstream without cascading upstream breakers.
Dimensions are 45 mm wide, 106 mm high, and 97 mm deep, with required clearances of 50 mm above and below, 30 mm to the sides, and zero forward or backward clearance needed. The compact footprint leaves room for adjacent devices in a crowded enclosure. Main circuit connections use spring-loaded terminals, accepting 2x (0.5 to 4 mm²) solid or stranded wire. A 3 mm screwdriver shaft is specified for the terminal screws. Mounting position is any, giving flexibility for horizontal or vertical busbar arrangements in the panel.