Rated breaking capacity hits 100 kA at 240 V, 400 V, and 500 V, dropping to 10 kA at 690 V. The gL/gG fuse coordination values are 25 A at 400 V and 500 V, 20 A at 690 V, so if you do back it with fuses for a higher SCCR, those are the maximum ratings.
Width is 45 mm, depth 97 mm, height 106 mm — that's a single 45 mm module on the DIN rail, leaving room alongside contactors or overloads. Mounting position any, so vertical or horizontal panel layouts work.