Rated at 6.3 A at both 480 V and 600 V, with a 100 kA short-circuit current rating (SCCR) at 240 V, 400 V, and 500 V, this breaker can safely interrupt high-fault currents without upstream coordination issues in most industrial panels.
Screw-type terminals on the main circuit accept 2×(0.5…1.5 mm²) or 2×(0.75…2.5 mm²) solid or stranded conductors, terminated with M3 screws. No special tooling needed — a standard PZ1 screwdriver handles the install. Clearance requirements: 50 mm above and below, 30 mm to the side, zero front and back — keeps the arc chamber vented and prevents heat buildup between adjacent breakers.