Skip to main content
Siemens 3RV2011-1GA15-ZW97 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1GA15-ZW97 SIRIUS Motor Protection Circuit B

MPN3RV2011-1GA15-ZW97
Active

Siemens SIRIUS motor protection circuit breaker, 3RV2011-1GA15-ZW97, Trip Class 10, 100 kA breaking capacity at 400 V, 45 mm wide, DIN rail mount.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

3RV2011-1GA15-ZW97 — Identification
ParameterValue
SeriesSIRIUS
Product designationCircuit breaker
Frame sizeS00
3RV2011-1GA15-ZW97 — Electrical
ParameterValue
Rated operational current (Ie)6.3 A
Rated voltage20 ... 690 V
Rated voltage, AC-3 (max.)690 V
Rated frequency50 ... 60 Hz
Rated insulation voltage (Ui), pollution degree 3690 V
Rated impulse withstand voltage (Uimp)6 kV
Number of poles3
Power loss (AC, hot)7.25 W
Power loss, per pole (AC, hot)2.4 W
3RV2011-1GA15-ZW97 — Protection & Tripping
ParameterValue
Overload release setting range4.5 ... 6.3 A
Instantaneous short-circuit trip current82 A
Trip classCLASS 10
Breaking capacity at 240 V (AC)100 kA
Breaking capacity at 400 V (AC)100 kA
Breaking capacity at 500 V (AC)100 kA
Breaking capacity at 690 V (AC)6 kA
Breaking capacity at 240 V100 kA
Breaking capacity at 690 V4 kA
Short-circuit trip typemagnetic
Overload release typethermal
Short-circuit protectionYes
Phase-failure detectionYes
Ground-fault detectionNo
Auxiliary switch extendableYes
3RV2011-1GA15-ZW97 — Endurance & Switching
ParameterValue
Endurance, main contacts (typ.)100 000
Endurance, auxiliary contacts (typ.)100 000
Switching frequency, AC-3 (max.)15 1/h
Auxiliary CO (changeover) contacts0
3RV2011-1GA15-ZW97 — Connections
ParameterValue
Main-circuit terminal typescrew-type terminals
Main-circuit connector arrangementTop and bottom
Conductor cross-section, solid / stranded2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
Conductor cross-section, finely stranded with ferrule2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
3RV2011-1GA15-ZW97 — Mechanical
ParameterValue
Height97 mm
Width45 mm
Depth97 mm
Mounting methodscrew and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715
Mounting positionany
3RV2011-1GA15-ZW97 — Environmental
ParameterValue
Operating temperature-20 ... +60 °C
Storage temperature-50 ... +80 °C
Transport temperature-50 ... +80 °C
Relative humidity (operation)10 ... 95 %
Max. installation altitude2 000 m
3RV2011-1GA15-ZW97 — Specifications
ParameterValue
Design Of The ProductFor motor protection

Product details

It's the go-to for a panel builder who needs a compact, DIN-rail-mounted breaker that coordinates with a contactor and overload relay in a motor starter. Rated Trip Class 10, it clears overloads quickly enough to protect standard motor windings during a locked-rotor event. No ground-fault detection here — that's handled separately if the application requires it.

Dimensions are 45 mm wide by 97 mm deep by 97 mm high. Mount in any orientation. Main contact screws are M3. The compact size leaves room for auxiliary contacts or a shunt trip in the same panel cell.

If you're comparing against the 3RV2021-1GA15, note that the 3RV2021 series is a physically larger frame (55 mm wide) with higher continuous current ratings — it won't drop into a panel cutout or DIN-rail layout designed for the 45 mm 3RV2011 without rework.

Frequently asked questions

What is the breaking capacity of this circuit breaker?

100 kA at 240 V, 400 V, 480 V, and 500 V. At 690 V it derates to 4 kA.

Where can I buy the 3RV2011-1GA15-ZW97?

We source this part through our independent distribution network. Submit an RFQ and we'll confirm current availability and pricing at quote time.

Does this breaker detect phase failure?

Yes, phase failure detection is included. Ground fault detection is not built in.

What backup fuse ratings are recommended?

gL/gG fuses: 50 A at 400 V, 40 A at 500 V, 35 A at 690 V.

MPN