Siemens 3RV2011-1JA25-Z W96 — Motor Protection Circuit Breakers (MPCB)

Siemens 3RV2011-1JA25-Z W96 SIRIUS Motor Protector, 7-10A, C

MPN3RV2011-1JA25-Z W96
Active

Siemens SIRIUS 3RV2 motor starter protector, size S00, Class 10, A-release 7...10 A, N-release 130 A, spring-type terminal, 1 NO + 1 NC auxiliary, multi-unit packaging (16 units).

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Specifications

3RV2011-1JA25-Z W96 — Specifications
ParameterValue
Group codeR711
Product group5332
Product classA: Standard product which is a stock item could be returned within the returns guidelines/period.
SeriesSIRIUS 3RV2 motor starter protectors
Export control regulationsAL : N / ECCN : N
Compliance with the substance restrictions according to RoHS directiveSince: 01-10-09

Product details

Motor protection circuit breaker, size S00, 7-10 A

The Siemens 3RV2011-1JA25-Z W96 is a SIRIUS 3RV2 motor starter protector in size S00, designed for motor protection with a Class 10 trip characteristic. The A-release (overload) is adjustable 7...10 A, and the N-release (short-circuit) is fixed at 130 A. This means it protects a motor drawing up to 10 A full-load current, with short-circuit protection coordinated to clear faults before the motor winding sees damaging energy — the Class 10 curve gives a 10-second maximum trip time at 7.2× the set current, which is the standard for standard-duty induction motors driving pumps, fans, and conveyors.

Termination and auxiliary contacts

The integrated transverse auxiliary switch provides 1 NO + 1 NC contact, enough for a remote run-status signal and a fault indication back to the PLC. Multi-unit packaging ships 16 units per pack, so a panel builder ordering for a multi-motor line gets consistent batch traceability.

Frequently asked questions

What is the A-release and N-release rating on this motor protector?

The A-release (overload protection) is adjustable from 7 to 10 A. The N-release (short-circuit protection) is fixed at 130 A. This combination is sized for a motor with a full-load current up to 10 A, with short-circuit coordination up to the N-release value.

MPN
3RV2011-1JA25-Z W96