Skip to main content
Siemens 3VA1010-2ED32-0BA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-2ED32-0BA0 SENTRON MCCB, 100 A, 3-Pole, TM21

MPN3VA1010-2ED32-0BA0

Siemens SENTRON 3VA1010-2ED32-0BA0, molded case circuit breaker, 3-pole, 100 A, TM210 thermal-magnetic trip, 52.5 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-2ED32-0BA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VA1010-2ED32-0BA0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED32-0BA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1010-2ED32-0BA0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED32-0BA0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VA1010-2ED32-0BA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED32-0BA0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

SENTRON 3VA1010-2ED32-0BA0 — 100 A MCCB with TM210 Trip Unit

The Siemens 3VA1010-2ED32-0BA0 is a SENTRON molded case circuit breaker (MCCB) rated for 100 A continuous current, configured as a 3-pole line-protection device with a TM210 thermal-magnetic trip unit. At 240 V it interrupts 52.5 kA; at 415 V that drops to 32 kA, at 440 V to 13.6 kA, and at 690 V to 7.5 kA — so the available fault current at the panelboard determines which voltage class governs the installation.

Current Derating and Thermal Profile

The 100 A rating holds flat from 40 °C through 50 °C. At 55 °C it derates to 96 A, at 60 °C to 94 A, at 65 °C to 92 A, and at 70 °C to 90 A. If the panel ambient runs above 50 °C, the continuous load must be reduced accordingly — the 90 A floor at 70 °C still leaves headroom for most motor circuits, but a 100 A continuous load in a hot enclosure will nuisance-trip on the thermal element.

The breaker measures 130 mm high, 76.2 mm wide, and 70 mm deep. Three-pole width at 76.2 mm is standard for a 100 A frame — it occupies one 3-pole space in a SENTRON distribution panelboard or a separate enclosure. Operating temperature range is -25 °C to 70 °C; storage range is -40 °C to 80 °C.

Frequently asked questions

What is the breaking capacity of 3VA1010-2ED32-0BA0 at different voltages?

At 240 V it interrupts 52.5 kA, at 415 V it interrupts 32 kA, at 440 V it interrupts 13.6 kA, and at 690 V it interrupts 7.5 kA. Select the rating that matches the available fault current at the panel voltage.

Does 3VA1010-2ED32-0BA0 include an undervoltage release?

Yes, it is equipped with an undervoltage release (UVR) as the auxiliary release, designated by the integrated auxiliary trip part number 3VA9608-0BB11.

What is the continuous current rating and how does it derate with temperature?

The rated continuous current Iu is 100 A, holding flat from 40 °C to 50 °C. It derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C.

Where can I buy 3VA1010-2ED32-0BA0 and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or lead-time figures are published here.

MPN