Skip to main content
Siemens 3VA1010-2ED32-0BC0 — Molded Case Circuit Breakers (MCCB)

Siemens SENTRON 3VA1010-2ED32-0BC0 MCCB, 100 A, 52.5 kA

MPN3VA1010-2ED32-0BC0

Siemens SENTRON 3VA1010-2ED32-0BC0, molded case circuit breaker, 3-pole, 100 A, TM210 release, 52.5 kA at 240 V, undervoltage release, 2 auxiliary switches HQ.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-2ED32-0BC0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
Basic switch (supplied) ref.3VA10102ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-2ED32-0BC0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C96 A
Current at 60 °C94 A
Current at 65 °C92 A
Current at 70 °C90 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1010-2ED32-0BC0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VA1010-2ED32-0BC0 — Construction & Connection
ParameterValue
Main circuit connection typelug terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-2ED32-0BC0 — Accessories & Functions
ParameterValue
Undervoltage releaseYes
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1010-2ED32-0BC0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-2ED32-0BC0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

The Siemens SENTRON 3VA1010-2ED32-0BC0 is a 3-pole molded case circuit breaker rated 100 A continuous at 40 °C, with a TM210 thermal-magnetic overcurrent release. It holds 100 A all the way to 50 °C before the first derate step — at 55 °C it's 96 A, at 70 °C it's 90 A, so the thermal curve is generous for a warm panel. The interrupting ratings climb to 52.5 kA at 240 V and 32 kA at 415 V, with 13.6 kA at 440 V and 7.5 kA at 690 V. That's enough SCCR headroom for most 480Y/277 V distribution boards and motor control centers without cascading upstream.

Frequently asked questions

How do I get current pricing and availability for 3VA1010-2ED32-0BC0?

This part is sourced to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time.

What is the 3VA1010-2ED32-0BC0's interrupting rating at 415 V?

It's rated 32 kA at 415 V, with 52.5 kA at 240 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

What compliance documentation does Siemens provide for this MCCB?

As a SENTRON molded case circuit breaker, it carries IEC 60947-2 compliance and is UL/CSA listed per Siemens standard declarations. RoHS and REACH declarations are available through Siemens documentation.

MPN
3VA1010-2ED32-0BC0