Skip to main content
Siemens 3VA1010-3ED32-0AE0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1010-3ED32-0AE0 SENTRON MCCB, 100A, 75.6kA@240V

MPN3VA1010-3ED32-0AE0

Siemens SENTRON 3VA1010-3ED32-0AE0, molded case circuit breaker, 3-pole, 100 A at 40 °C, TM210 overcurrent release, line protection, breaking capacity 75.6 kA at 240 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1010-3ED32-0AE0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10103ED320AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AA12
3VA1010-3ED32-0AE0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C100 A
Current at 45 °C100 A
Current at 50 °C100 A
Current at 55 °C98 A
Current at 60 °C96 A
Current at 65 °C94 A
Current at 70 °C91 A
Switching capacity classN
Breaking capacity at 240 V75.6 kA
Breaking capacity at 415 V52.5 kA
Breaking capacity at 440 V32 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.25 W
3VA1010-3ED32-0AE0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1010-3ED32-0AE0 — Construction & Connection
ParameterValue
Main circuit connection typenut keeper kit on both ends
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1010-3ED32-0AE0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts4
3VA1010-3ED32-0AE0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1010-3ED32-0AE0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

Breaking capacity is 75.6 kA at 240 V, stepping down to 52.5 kA at 415 V and 32 kA at 440 V. It ships with provision for up to four HQ auxiliary switches if you need status feedback to a PLC.

Current derating and thermal behaviour

Above that it derates linearly: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, 91 A at 70 °C. If your panel internal temperature hits 60 °C, plan for 96 A continuous load maximum. Maximum power loss is 25 W — that's the heat the breaker dumps into the enclosure at full rated current.

The width is a standard 3-inch (76.2 mm) footprint for 3-pole MCCBs in this class — drops into most panel-mounted breaker bases without adaptor plates. That covers unheated warehouses and outdoor enclosures in most climates.

MPN
3VA1010-3ED32-0AE0