Siemens SENTRON 3VA1063-2ED36-0AA0 — 63 A MCCB, Line Protection, TM210 Release
Breaking capacity varies with line voltage: 52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. The 63 A rating holds flat from 40 °C to 50 °C, then derates slightly to 58 A at 70 °C — useful to know if the panel runs hot. Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — a standard 3-pole MCCB footprint that fits most DIN-rail or panel-mount enclosures.