Skip to main content
Siemens 3VA1063-2ED36-0AF0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-2ED36-0AF0 SENTRON MCCB, 63 A, 52.5 kA

MPN3VA1063-2ED36-0AF0

Siemens SENTRON 3VA1063-2ED36-0AF0, molded case circuit breaker, 3-pole, 63 A, TM210 thermal-magnetic release, breaking capacity 52.5 kA at 240 V / 32 kA at 415 V, IP40 front, 70 × 76.2 × 130 mm.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1063-2ED36-0AF0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Basic switch (supplied) ref.3VA1063-2ED36-0AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1063-2ED36-0AF0 — Ratings
ParameterValue
Number of poles3
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C60.48 A
Current at 60 °C59.22 A
Current at 65 °C57.96 A
Current at 70 °C56.7 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 690 V7.5 kA
3VA1063-2ED36-0AF0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
3VA1063-2ED36-0AF0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-2ED36-0AF0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts2
3VA1063-2ED36-0AF0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-2ED36-0AF0 — Mechanical
ParameterValue
Height130 mm
Width76.2 mm
Depth70 mm

Product details

63 A MCCB with TM210 release — panel fit and breaking capacity

The Siemens SENTRON 3VA1063-2ED36-0AF0 is a 3-pole molded case circuit breaker rated for continuous 63 A at 40 °C, with no derating needed up to 50 °C (still 63 A). Above that, it steps down to 60.48 A at 55 °C and 56.7 A at 70 °C — useful when the breaker sits in a warm enclosure near other heat sources. Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. That 52.5 kA at 240 V is high enough for most industrial service-entrance or feeder applications where fault current is substantial; the 7.5 kA at 690 V still clears a fault on a 690 V motor branch circuit without cascading upstream.

Panel footprint and mounting

Dimensions are 70 mm deep, 76.2 mm wide, 130 mm tall — a standard SENTRON 3VA frame size that fits the same cutout and bus-bar spacing as other 3VA1 breakers.

Frequently asked questions

What is the breaking capacity of 3VA1063-2ED36-0AF0 at different voltages?

Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V.

What is the difference between 3VA1063-2ED36-0AF0 and 3VA1010-2ED36-0AC0?

The 3VA1010-2ED36-0AC0 is a lower-rated frame (10 A vs 63 A) with the same TM210 release type and auxiliary switch configuration. Panel cutout dimensions are the same 3VA frame size, so it drops into the same mounting footprint without rewiring the bus bars — but the continuous current rating is the deciding factor for the BOM line.

Where can I buy 3VA1063-2ED36-0AF0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN