Skip to main content
Siemens 3VA1063-2ED36-0AH0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VA1063-2ED36-0AH0 SENTRON MCCB, 63A, 52.5kA at 240V

MPN3VA1063-2ED36-0AH0

Siemens SENTRON 3VA1063-2ED36-0AH0, 3-pole molded case circuit breaker, 63 A (40 °C), TM210 thermal-magnetic release, 52.5 kA at 240 V, line protection design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3VA1063-2ED36-0AH0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Basic switch (supplied) ref.3VA10632ED360AA0
Integrated auxiliary / alarm switch ref.3VA9988-0AB12
3VA1063-2ED36-0AH0 — Ratings
ParameterValue
Number of poles3
Rated operational voltage Ue (AC)690 V
Rated insulation voltage Ui800 V
Current at 40 °C63 A
Current at 45 °C63 A
Current at 50 °C63 A
Current at 55 °C62 A
Current at 60 °C61 A
Current at 65 °C60 A
Current at 70 °C58 A
Switching capacity classB
Breaking capacity at 240 V52.5 kA
Breaking capacity at 415 V32 kA
Breaking capacity at 440 V13.6 kA
Breaking capacity at 500 V7.5 kA
Breaking capacity at 690 V7.5 kA
Power loss, max.17.3 W
3VA1063-2ED36-0AH0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
Grounding protection functionNo
3VA1063-2ED36-0AH0 — Construction & Connection
ParameterValue
Main circuit connection typebox terminal on both sides
Main circuit connector arrangementFront terminal
Protection class (IP), frontIP40
3VA1063-2ED36-0AH0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorYes
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts3
3VA1063-2ED36-0AH0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VA1063-2ED36-0AH0 — Mechanical
ParameterValue
Mechanical service life (operating cycles), typ.20 000
Height130 mm
Width76.2 mm
Depth70 mm
Height (in)5.12 in
Width (in)3 in
Depth (in)2.76 in

Product details

It carries a continuous rating of 63 A at 40 °C, with minimal thermal derating up to 70 °C (58 A at 70 °C), so it holds its full ampacity across typical enclosure ambient conditions. Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, and 7.5 kA at 690 V — figures that cover most industrial service-entrance and feeder applications in North American and IEC systems.

Integration Notes

Width is 76.2 mm (3 in), depth 70 mm (2.76 in), height 130 mm (5.12 in) — fits standard 3-pole MCCB cutouts in 200 A and smaller panelboards. The box lug terminals accept copper or aluminum conductors up to the breaker's terminal rating (verify lug spec against wire gauge at installation). If the application needs remote tripping or GF protection, order the accessory module separately (Siemens 3VA9 series).

The storage minimum covers cold warehouse conditions; the operating minimum matters if the breaker must close under load at sub-freezing temperatures.

Frequently asked questions

How do I get current pricing and availability for 3VA1063-2ED36-0AH0?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time through independent distribution channels; no public price or live stock count is maintained on the product page.

Will 3VA1063-2ED36-0AH0 drop into a panel specified around 3VA1110-5EF32-0AM0?

No — the 3VA1110-5EF32-0AM0 is a 100 A frame with electronic release and different mounting footprint. The 63 A 3VA1063 frame shares the same SENTRON 3VA platform but uses a smaller physical package; cutout dimensions and bus-bar spacing differ. Verify panel layout before substituting.

What compliance documentation does this brand provide for 3VA1063-2ED36-0AH0?

Siemens SENTRON 3VA breakers carry IEC 60947-2 certification, UL 489 listing, and CE marking. RoHS and REACH declarations are available in the Siemens Industry Online Support documentation for the 3VA series.

What is the breaking capacity at 415 V?

32 kA at 415 V AC. This covers most European 400 V distribution systems with typical fault levels below 25 kA, leaving headroom for transformer-fed installations.

MPN
3VA1063-2ED36-0AH0