Skip to main content
Siemens 3VM1132-4ED12-0AA0 — Molded Case Circuit Breakers (MCCB)

Siemens 3VM1132-4ED12-0AA0 SENTRON MCCB, 1-pole, 32 A, 76 kA

MPN3VM1132-4ED12-0AA0
Active

Siemens SENTRON 3VM1132-4ED12-0AA0, 1-pole molded case circuit breaker, 32 A rated, 76 kA at 240 V AC, TM210 thermal-magnetic release, line protection version.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

3VM1132-4ED12-0AA0 — Identification
ParameterValue
Product designationMolded case circuit breaker
Brand / rangeSENTRON
Product versionLine protection
3VM1132-4ED12-0AA0 — Ratings
ParameterValue
Number of poles1
Rated operational voltage Ue (AC)415 V
Current at 40 °C32 A
Current at 45 °C32 A
Current at 50 °C32 A
Current at 55 °C31 A
Current at 60 °C31 A
Current at 65 °C30 A
Current at 70 °C30 A
Switching capacity classS
Breaking capacity at 240 V76 kA
Breaking capacity at 415 V9 kA
Power loss, max.4 W
3VM1132-4ED12-0AA0 — Protection & Trip Unit
ParameterValue
Overcurrent release (trip unit) typeTM210
Overcurrent protection functionLI
Ground-fault monitoringWithout
3VM1132-4ED12-0AA0 — Construction & Connection
ParameterValue
Main circuit connector arrangementFront connection
Protection class (IP), frontIP40
3VM1132-4ED12-0AA0 — Accessories & Functions
ParameterValue
Undervoltage releaseNo
Voltage triggerNo
Trip indicatorNo
Communication functionNo
Measurement functionNo
Motor drive optionNo
Auxiliary CO contacts0
3VM1132-4ED12-0AA0 — Environmental
ParameterValue
Operating temperature, max.70 °C
Operating temperature, min.-25 °C
Storage temperature, max.80 °C
Storage temperature, min.-40 °C
3VM1132-4ED12-0AA0 — Mechanical
ParameterValue
Height130 mm
Width25.4 mm
Depth70 mm
Height (in)5.12 in
Width (in)1 in
Depth (in)2.76 in

Product details

It carries a 32 A continuous rating at 40 °C and holds that rating through 50 °C — at 55 °C it derates to 31 A, and at 70 °C to 30 A, so in a warm panel you lose only a couple amps. Breaking capacity is 76 kA at 240 V AC and 9 kA at 415 V AC, which covers most industrial service-entrance and feeder applications on the lower voltage side; at 415 V the 9 kA figure is adequate for downstream distribution but not for high-fault utility tie points.

Mounting and fit

Width is 25.4 mm (1 inch) — a single 1-pole module that snaps onto standard DIN rail. Depth of 70 mm and height of 130 mm mean it fits in shallow enclosures where a full-frame MCCB might not.

Frequently asked questions

What is the breaking capacity of 3VM1132-4ED12-0AA0?

76 kA at 240 V AC and 9 kA at 415 V AC. The 415 V figure is suitable for downstream distribution but not for high-fault utility tie points.

Where can I buy 3VM1132-4ED12-0AA0?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does 3VM1132-4ED12-0AA0 have a trip indicator or undervoltage release?

No. This variant has no trip indicator and no undervoltage release. For those features, a different option code within the 3VM family would be needed.

MPN
3VM1132-4ED12-0AA0