The Siemens 3VM1163-5ED42-0AA0 is a 4-pole IEC frame 160 molded-case circuit breaker rated for line protection. It carries a 63 A thermal-magnetic trip unit (TM210) with fixed overload protection at Ir = 63 A and a short-circuit pickup set at Ii = 10 × In, meaning the magnetic trip fires at 630 A. The interrupting rating hits 55 kA at 415 V AC (breaking capacity class M), which covers most industrial secondary-distribution panels feeding motor control centers or lighting sub-distribution.
Compliance and documentation
RoHS compliant since 01 June 2012. REACH Article 33 disclosure applies: lead (CAS 7439-92-1) above 0.1% w/w in the candidate list. Export control is AL N / ECCN N — no special licensing for cross-border trade. The packaging dimensions are 150 × 119 × 116 mm, single-piece quantity.