It protects against overcurrent and earth faults in a single device, saving DIN-rail space compared to separate MCB + RCD. Rated 32 A at 30 °C ambient, it derates to 29.1 A at 40 °C, 27.8 A at 45 °C, 26.6 A at 50 °C, and 25 A at 55 °C — so the real-world current capacity depends on your enclosure temperature. The C-curve trip characteristic means it holds 5–10× rated current for short periods, suited to motor and lighting loads with moderate inrush.
Occupies 6 modular width units (108 mm wide) on a DIN rail. Mounting position any orientation. Halogen-free and silicon-free construction, which matters for clean-room or corrosive-environment specs.
Environmental range and compliance
That cold-end rating is unusual for a combined RCD/MCB — suitable for unheated enclosures in cold climates or refrigeration lines. Lifecycle stage is current production.