The Siemens 5SY7113-6 is a 1-pole SENTRON miniature circuit breaker (MCB) with a B tripping characteristic and a 13 A rated current at 400 V AC. It snaps onto a DIN rail (quick assembly system) in any mounting position, taking up 1 MWU (18 mm wide, 76 mm deep, 90 mm tall).
Breaking capacity and what it means for your circuit
Rated at 15 kA per EN 60898 and 25 kA per IEC 60947-2, this MCB safely interrupts fault currents up to those levels without welding or cascading upstream. The higher IEC figure applies when the breaker is used as an industrial circuit breaker per IEC 60947-2 — the standard that governs industrial switchgear rather than household installations. For UL 1077 / CSA C22.2 No. 235 applications, the interrupting capacity is 5 kA at AC. That's the number to check if your panel is built to North American supplementary-protector rules.
B-curve trip and environmental tolerance
The MCB operates from -40 °C to 75 °C ambient, with humidity derating above 55 °C.