Breaker spec at a glance
The D-curve (10–20× In) is built for loads with high inrush — think motor starters, small transformers, or solenoid banks where a B- or C-curve would nuisance-trip on startup. At 13 A it handles a 3–4 kW motor on 400 V three-phase without issue. Thermal derating is published per degree: 13 A at 35 °C, 12.38 A at 40 °C, 12.05 A at 45 °C, 11.73 A at 50 °C, 11.38 A at 55 °C, 11.02 A at 60 °C.
Snaps onto DIN rail via quick-assembly system, one modular width (18 mm). Mount in any position; pollution degree 3.
Rated for mechanical engineering and industry per the suitability listing.