Integration & Ratings
Snap-on mounting for DIN rail (1 MW wide at 18 mm), any mounting position, 70 mm installation depth. Rated IP20 with conductors connected — suitable for enclosed panel environments, not washdown.
Thermal Derating
The C13 rating is at 35 °C ambient. At 40 °C derate to 12.38 A; at 50 °C to 11.73 A; at 60 °C to 11.02 A. For a panel running warm (say 50 °C internal ambient), size the load to 11.7 A continuous to avoid nuisance tripping.