Skip to main content
Siemens 5SY7113-7 — 1-Pole MCB (DIN Rail)

Siemens 5SY7113-7 SENTRON MCB, 1P C13, 15kA/25kA

MPN5SY7113-7
Active

Siemens SENTRON 5SY7113-7 miniature circuit breaker, 1-pole, C-curve, 13 A, 15 kA (EN 60898) / 25 kA (IEC 60947-2), 1 MW, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SY7113-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles1
Application suitabilityMechanical engineering / industry
5SY7113-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)15 kA
Energy limitation class3
Overvoltage categoryIII
5SY7113-7 — Mounting & Connection
ParameterValue
Mounting positionany
Fastening methodQuick assembly system
Combined terminal, topYes
Combined terminal, bottomYes
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SY7113-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree3
Halogen-freeYes
Silicone-freeYes

Product details

Integration & Ratings

Snap-on mounting for DIN rail (1 MW wide at 18 mm), any mounting position, 70 mm installation depth. Rated IP20 with conductors connected — suitable for enclosed panel environments, not washdown.

Thermal Derating

The C13 rating is at 35 °C ambient. At 40 °C derate to 12.38 A; at 50 °C to 11.73 A; at 60 °C to 11.02 A. For a panel running warm (say 50 °C internal ambient), size the load to 11.7 A continuous to avoid nuisance tripping.

Frequently asked questions

What is the breaking capacity of 5SY7113-7?

15 kA per EN 60898 and 25 kA per IEC 60947-2 — the IEC figure applies in industrial panels where fault current can exceed 15 kA.

Where can I buy 5SY7113-7?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

Will 5SY7113-7 drop into a panel specified for 5SY7140-8CC?

Both are 1 MW SENTRON MCBs with the same footprint (18 mm width, 70 mm installation depth). The 5SY7140-8CC is a different rating (40 A, C-curve); physical fit is identical, but the load current must match the circuit design.

MPN
5SY7113-7