Skip to main content
Siemens 6ES7317-7UL10-0AB0 — PLCs (Programmable Logic Controllers)

Siemens 6ES7317-7UL10-0AB0 CPU 317F-2 PN/DP, FM 8, PROFIsafe

MPN6ES7317-7UL10-0AB0
End of Life

Siemens SIMATIC S7-300 CPU 317F-2 PN/DP, SFB type, FM 8, CFC, FBD, LAD, SCL, STL, GRAPH, HiGraph, IRT, PROFIsafe, 244 byte inputs/outputs, 4 counters, integrated PROFINET interface.

$5,643.88 – $12,028.00Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

6ES7317-7UL10-0AB0 — I/O
ParameterValue
Digital inputs4
Digital outputs8
ExpandableNo
Input data area244 byte
Output data area244 byte
6ES7317-7UL10-0AB0 — Processor & Memory
ParameterValue
Execution time, bit operations (typ.)0.025 µs
Execution time, word operations (typ.)0.03 µs
Execution time, floating-point arithmetic (typ.)0.16 µs
Size, max.4 096 byte
6ES7317-7UL10-0AB0 — Programming
ParameterValue
Programming language: FBDYes
Programming language: LADYes
Programming language: SCLYes
6ES7317-7UL10-0AB0 — Electrical
ParameterValue
Rated value (DC)24 V
Current consumption (rated)1 100 mA
Permissible range, lower limit (DC)19.2 V
Permissible range, upper limit (DC)28.8 V
Power loss (typ.)8.5 W
Short-circuit protectionYes
6ES7317-7UL10-0AB0 — Environmental
ParameterValue
Temperature, min.0 °C
Temperature, max.60 °C
6ES7317-7UL10-0AB0 — Mechanical
ParameterValue
Width120 mm
Height125 mm
Depth130 mm
Weight (approx.)640 g
6ES7317-7UL10-0AB0 — Communication
ParameterValue
Interface typePROFINET

Product details

CPU 317F-2 PN/DP — safety-rated controller with FM 8 and full IEC 61131-3 language set

The Siemens 6ES7317-7UL10-0AB0 is a SIMATIC S7-300 CPU 317F-2 PN/DP, an SFB-type safety controller with FM 8 firmware. It runs CFC, FBD, LAD, SCL, STL, GRAPH, and HiGraph — the full IEC 61131-3 language set plus high-level technology sequencing. The integrated PROFINET interface supports IRT, UDP, TCP/IP, and PROFIsafe, making this the safety-capable CPU for a mixed standard/safety line where you need one controller handling both the logic and the SIL-rated loop.

What FM 8 and the language set mean for your project

FM 8 is the firmware version — it determines which STEP 7 and technology packages you need. This CPU requires STEP 7 V5.5 SP2 or higher plus S7-Technology Option Package V4.2 SP3, S7 F Configuration Pack V5.5 SP10, and S7 Distributed Safety Option Package V5.4 SP5. If your plant engineering standard is still on V5.4, you'll need to upgrade the toolchain before you can download to this CPU. The CFC (Continuous Function Chart) support means you can build signal-flow diagrams for process loops without writing STL — useful for batch or continuous processes where the controls engineer thinks in blocks, not ladder. The 244-byte input and output process-image areas, plus 4 counters with a 1 A²·s I²t rating, size this for medium I/O counts — think a packaging machine with 6 servo axes and 80 prox sensors, not a 2000-I/O conveyor system. The 8 CP connections for LAN and 8 for PtP give you headroom for HMI, SCADA, and barcode scanners without a separate switch.

PROFIsafe and safety routing — one CPU for standard and safety

The CPU routes safety telegrams over the same PROFINET cable as standard IO — the safety layer is in the protocol, not a separate bus. That saves a rack slot and simplifies the wiring cabinet. The RS 485 interface is available for legacy drives or Modbus RTU devices, though the primary fieldbus is PROFINET. For DP slaves, you'll need a CP (2 max). The 120 mm width, 125 mm height, and 130 mm depth fit the standard S7-300 rack footprint. It clips onto the DIN rail same as any 317 — no special mounting bracket. The 0 °C to 60 °C operating range covers most cabinet environments but watch the derating if this sits above a row of drives.

Frequently asked questions

What is the FM 8 firmware version on this CPU?

The CPU carries FM 8 firmware, which requires STEP 7 V5.5 SP2 or higher plus the specific technology and safety option packages listed in the specs.

Does this CPU support PROFIsafe?

Yes, PROFIsafe is integrated — no separate fail-safe module needed. Safety telegrams route over the same PROFINET cable as standard IO.

What programming languages does 6ES7317-7UL10-0AB0 support?

It supports CFC, FBD, LAD, SCL, STL, GRAPH, and HiGraph — the full IEC 61131-3 set plus high-level technology sequencing.

Where can I buy 6ES7317-7UL10-0AB0?

This CPU is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
6ES7317-7UL10-0AB0