Drive ratings that define the commissioning envelope
The 6SL3225-0BE33-0UA0 is a SINAMICS G120 Power Module PM250 without integrated filter, designed for regenerative operation on 3-phase 380-480 VAC supplies at 47-63 Hz. Under high overload duty, it delivers 30 kW continuously with 200 % overload for 3 seconds and 150 % for 57 seconds, at 0 to +50 °C ambient — this is the rating for pump, fan, or conveyor applications where peak torque is infrequent. Under light overload duty, the continuous output rises to 37 kW with 150 % for 3 seconds and 110 % for 57 seconds, but the ambient ceiling drops to +40 °C — the thermal budget shifts, so panel airflow and derating must be verified against the load profile. The regenerative capability means the DC bus can feed energy back to the line during deceleration, eliminating the need for a braking resistor in most applications — the PM250 handles this internally without an external chopper module.
Active production and ordering posture
Lifecycle status is active per Siemens — no end-of-life notice or last-time-buy window is in effect, so the part is a stable BOM line for new designs and MRO spares. The product class is C — manufactured or produced to order, not stocked as a standard catalogue item. This means lead time and volume pricing are confirmed at RFQ, and the unit is traceable to the production batch for validation documentation packages. RoHS compliance is confirmed since 18 May 2016. REACH Article 33 disclosure notes lead (CAS 7439-92-1) above 0.1 % w/w — this is the standard declaration for solder joints and termination plating; the part remains compliant for EU industrial installation.
The power module measures 499 x 275 x 204 mm (H x W x D) with IP20 finger-safe protection — it is intended for enclosure mounting where the front face is accessible but live parts are behind the gland plate or door. Packaging dimensions are 600 x 400 x 310 mm, single-piece quantity — the drive ships individually, so kitting multiples for a panel build requires separate ordering per unit. No control unit or BOP (Basic Operator Panel) is included — the PM250 is a power stage only; a separate CU240x control unit must be ordered and mounted on the interface slot before commissioning.