Skip to main content
Schneider Electric A9F04163

Schneider Electric A9F04163 Acti9 iC60N MCB, 63 A, C Curve,

MPN A9F04163
Active

Schneider Electric Acti9 iC60N, A9F04163, miniature circuit breaker, 1P, 63 A, C curve, 36 kA Icu at 12-60 V AC, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9F04163 key specifications
ParameterValue
Control typeToggle
Network typeDC AC
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Insulation voltage ui500 V AC 50/60 Hz conforming to EN/IEC 60947-2
Breaking capacity36 kA Icu at 12...60 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 100...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 12...60 V DC conforming to EN/IEC 60947-2 10 kA Icu at 60...72 V DC conforming to EN/IEC 60947-2 6000 A Icn at 230 V AC 50/60 Hz conforming to EN/IEC 60898-1
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-35 °C

All specifications

A9F04163 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to EN/IEC 60947-2
ColorWhite
Depth78.5 mm
Width18 mm
Height91 mm
Electrical life cycles10000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-35...70 °C

Product details

The Schneider Electric A9F04163 is a 1-pole Acti9 iC60N miniature circuit breaker rated 63 A with a C curve. Breaking capacity is 36 kA Icu at 12-60 V AC and 20 kA Icu at 100-133 V AC per EN/IEC 60947-2, with an Icn of 6 kA at 230 V AC per EN/IEC 60898-1. That 36 kA figure at low voltage means this breaker handles high prospective fault currents common in transformer-fed panels without cascading upstream.

Trip curve and coordination

The C curve has a magnetic tripping threshold of 8 x In ±20 %, so it holds through motor inrush and capacitive loads up to roughly 500 A instantaneous before tripping. This makes it a standard choice for general distribution where moderate inrush exists but not the high peaks of a D curve.

Termination and environment

Double terminals accept 1-35 mm² rigid or 1-25 mm² flexible cable, with a tightening torque of 3.5 N.m and strip length of 14 mm. The IP20 finger-safe front and tropicalisation level 2 per IEC 60068-1 (95 % RH at 55 °C) mean it holds up in humid panel environments without condensation tracking.

MPN