A9N19854 MCB Acti9 C120L 3P 100A D Curve, 15 kA

MPN A9N19854
Active

Schneider Electric Acti9 C120L miniature circuit breaker, A9N19854, 3P, 100 A, D curve, 15 kA breaking capacity at 400 V AC.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9N19854 specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage400 V
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity15 kA Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 15 kA Icn at 400 V AC 50/60 Hz conforming to GB/T 10963.1 15 kA Icu at 400 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 400 V AC 50/60 Hz conforming to GB/T 14048.2
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C
Depth73 mm
Height81 mm
Electrical life cycles5000 cycles
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

The A9N19854 is a 3-pole miniature circuit breaker from the Acti9 C120L range, rated 100 A at 30 °C with a D curve. The D curve means magnetic tripping occurs at 10–14 × In (per GB 10963.1) or 12 × In ±20% (per GB/T 14048.2) — designed for loads with high inrush, like motor circuits or transformers, where a B or C curve would nuisance-trip on startup. That dual standard matters: 60898-1 covers household-type installation, while 60947-2 covers industrial panel duty — this one part satisfies both, so it fits a distribution board or an industrial sub-panel without a second look at the standard. Clip-on mounting to DIN rail (9 mm pitches) means it snaps into a standard 3-module width on the rail. The 73 mm depth and 81 mm height keep it within the envelope of a typical Acti9 distribution board — no surprises when you're laying out gland plates or calculating fill factor.

Integration notes

Tunnel-type terminals accept 1–50 mm² rigid (without cable end) or 1.5–35 mm² flexible (with or without ferrule). The toggle gives local ON/OFF indication and a contact position indicator confirms isolation status — useful for a field service tech verifying the circuit is dead before working downstream. Rated insulation voltage 500 V AC, impulse withstand 6 kV. Electrical durability 5000 cycles, mechanical 20,000 cycles — the mechanical figure governs panel life if the breaker is used as a disconnect switch rather than just overcurrent protection.

MPN
A9N19854