Skip to main content
Schneider Electric A9Z51216

Schneider Electric A9Z51216 Acti9 iID RCCB, 16A 30mA Type B-

MPN A9Z51216
Active

Schneider Electric Acti9 iID RCCB, 2P, 16 A, 30 mA, Type B-EV, 230 V AC, 50 Hz, DIN rail.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

A9Z51216 specifications
ParameterValue
Control typeToggle
Voltage230 V AC 50 Hz
Insulation voltage ui250 V
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3
ColorWhite
Depth79 mm
Width72 mm
Height88 mm
Electrical life cycles15000 cycles
Mechanical life cycles20000 cycles
ApplicationElectrical Vehicle charger
Operating temperature-25...60 °C

Product details

The A9Z51216 is a Schneider Electric Acti9 iID RCCB, 2-pole, rated 16 A at 230 V AC 50 Hz with 30 mA earth-leakage sensitivity. The Type B-EV classification per IEC 61008-2-1 and IEC/EN 62423 detects leakage profiles from EV chargers. Rated insulation voltage is 250 V; the overvoltage category is IV, meaning it's rated for installation at the origin of the low-voltage installation where transient overvoltages are highest. Pollution degree 3 confirms suitability for industrial environments with conductive or dry non-conductive pollution. The device clips onto a DIN rail, occupies 8 x 9 mm pitches (72 mm width), and is wired via double terminals accepting up to 35 mm² rigid or 25 mm² flexible conductors.

Deployment context: EV charging and general distribution

Schneider explicitly lists the device application as 'Electrical Vehicle charger'. In practice, this RCCB is installed as the outgoing group incomer or final-circuit protection in a distribution board feeding a wallbox or charging station. The Type B-EV characteristic is critical here: EV chargers generate smooth DC leakage currents from the onboard rectifier, which a standard Type A RCCB may not detect. This unit also carries the 8/20 µs impulse withstand rating of 3 kA per EN/IEC 61008-1, so it survives surge events on the supply side without nuisance tripping. The toggle provides ON/OFF indication and a trip indicator; a padlocking option is available for lockout/tagout during maintenance.

No successor or end-of-life notice is on record. For a BOM line specifying the A9Z51216, the fit is confirmed by the 16 A / 30 mA / Type B-EV / 2P / 230 V AC combination; there is no ambiguity in the order code.

Approvals and compliance documentation

Quality labels include VDE, NF, IMQ, and KEMA. Standards compliance is to IEC 61008-2-1 and IEC/EN 62423.

MPN
A9Z51216