Skip to main content
Schneider Electric C25F44V100

Schneider Electric C25F44V100 ComPacT NSX250F, 100 A, 85 kA

MPN C25F44V100
Active

Schneider Electric ComPacT NSX series, NSX250F, C25F44V100, 4-pole molded case circuit breaker, 100 A, MicroLogic 4.2 electronic trip unit, 85 kA Icu at 240 V AC.

$1,322.27 – $2,769.12 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25F44V100 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 15 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C25F44V100 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C25F44V100 is a 4-pole ComPacT NSX250F molded case circuit breaker rated 100 A at 40 °C, fitted with a MicroLogic 4.2 electronic trip unit that provides L (long-time), So (short-time with fixed delay), I (instantaneous), and R (earth-leakage) protection in a single device. Its breaking capacity hits 85 kA Icu at 240 V AC (EN/IEC 60947-2) and 36 kA Icu at 415 V AC, which gives solid selectivity headroom for distribution panels feeding downstream subfeeds or motor control centers.

Sizing and integration

IP40 front face, IK07 impact rating. Toggle control with a rotary IΔn switch for earth-leakage test/reset. Rated for 50/60 Hz networks, usable from 0 to 2000 m without derating, up to 5000 m with derating.