Skip to main content
Schneider Electric ENW13265

ENW13265 EasyPact NW Switch Disconnector, 630 A, 3P, Drawout

MPN ENW13265
Active

Schneider Electric EasyPact NW switch disconnector, ENW13265, 3 poles, 630 A AC-23A, drawout mount, 1000 V insulation, 50 kA short-time withstand.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW13265 key specifications
ParameterValue
Main product or component typeSwitch disconnector
Voltage440 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 630 A AC 50/60 Hz 440 V
Utilization categoryAC-23 A
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C

All specifications

ENW13265 additional specifications
ParameterValue
Pollution degreeclass 3
Depth277 mm
Width288 mm
Height322 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The ENW13265 is a 3-pole switch disconnector from the EasyPact NW range, rated 630 A in AC-23A utilisation category at 440 V AC — that is the motor-switching duty class, so it handles high inrush from inductive loads like conveyors or compressors without derating. It is a drawout (withdrawable) unit, meaning the switching element can be racked out from the cradle for safe isolation and maintenance while the enclosure stays wired.

Rated operational current is 630 A in AC-23A at 440 V — that is the current it can make and break repeatedly for motor loads. Below that, the rated short-time withstand current (Icw) is 50 kA for 1 second at 220–440 V, and the rated short-circuit making capacity (Icm) is 75 kA at the same voltage range. These numbers tell you the switch can survive and close into a fault up to 75 kA peak, and can carry 50 kA RMS for one second while upstream protection clears — critical for selective coordination studies. Rated insulation voltage (Ui) is 1000 V AC, and impulse withstand (Uimp) is 12 kV, so it is comfortable in 690 V systems or where transient overvoltages are common.

Mounting is drawout on a rail base plate — the fixed part (cradle) bolts into the enclosure, and the switch unit slides in and out. Connection pitch is 70 mm without a spreader, and connections are at the rear, vertical or horizontal orientation. Panel builders should allow for the 322 mm height, 288 mm width, and 277 mm depth when laying out the gland plate and busbar runs. IP30 protection means it is not washdown-rated but fine inside a locked enclosure.

No official successor exists because none is needed.