Skip to main content
Schneider Electric ENW13285

ENW13285 EasyPact NW Switch Disconnector, 1000 A, 3P, AC-23A

MPN ENW13285
Active

Schneider Electric EasyPact NW switch disconnector, ENW13285, 3-pole, 1000 A AC-23A at 440 V, fixed mount, IP30, IEC 60947-3.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW13285 key specifications
ParameterValue
Main product or component typeSwitch disconnector
Voltage440 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1000 A AC 50/60 Hz 440 V
Utilization categoryAC-23 A
IP ratingIP30
Terminal pitch70 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Storage temperature-40...85 °C without control unit

All specifications

ENW13285 additional specifications
ParameterValue
Pollution degreeclass 3
Depth196 mm
Width346 mm
Height301 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The ENW13285 is a 3-pole switch disconnector from the EasyPact NW range, rated 1000 A in AC-23A duty at 440 V — that's the utilisation category for switching motor loads and other highly inductive circuits, not just resistive. AC-23A covers occasional switching of motors, transformers, and capacitor banks, so this part is sized for distribution panels feeding motor control centres or heavy plant loads. The 50 kA short-time withstand (Icw) for 1 second and 75 kA making capacity (Icm) at 220–440 V mean it can hold in through a downstream fault and close onto a short circuit without welding contacts — critical for a main disconnector in an industrial switchboard. Rated insulation voltage (Ui) is 1000 V AC, impulse withstand (Uimp) is 12 kV, and it's certified for isolation per IEC 60947-3 — so it doubles as a visible-break isolating point for lockout/tagout.

Deployment context

Fixed-mount design on a rail base plate, with rear connection and a 70 mm connection pitch without spreader. Mechanical durability is 20,000 cycles with maintenance, 10,000 without; electrical durability under AC-23A at 440 V is 5,000 cycles without maintenance. That's a solid service life for a main disconnect that sees maybe a few operations per shift.

MPN