Skip to main content
Schneider Electric EVS40H3NF20

Schneider Electric EVS40H3NF20 EasyPact EVS Circuit Breaker,

MPN EVS40H3NF20
Active

Schneider Electric EasyPact EVS, circuit breaker, EVS40H3NF20, 4000 A, 65 kA Icu at 440 V AC, 3P, electrically operated.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS40H3NF20 specifications
ParameterValue
Control typeElectrically operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width422 mm
Height352 mm
ApplicationDistribution
Operating temperature-5...70 °C

Product details

That 4000 A continuous current serves the main feeder or a large transformer secondary in a distribution board. At 690 V the breaking capacity drops to 50 kA Icu, still substantial for industrial 690 V networks. The unit carries IEC 60947-2 certification, the standard for low-voltage switchgear and controlgear, and is suitability-for-isolation marked — meaning you can use it as a visible disconnect point without a separate switch.

Trip unit and protection

The EVS Trip System2.0 is an electronic trip unit with LI protection — overload long-time and instantaneous short-circuit. The 4000 A CT rating matches the breaker frame. Maximum breaking time is 25 ms, fast enough to limit let-through energy on a bolted fault.

Fixed-mount design on a rail or base plate. Rear connection with a 115 mm pitch without spreader — plan the bus bar drill pattern accordingly. Pollution degree 4 per IEC 60664-1 — the highest rating, for harsh industrial atmospheres with conductive dust or condensation. Mechanical durability is 20,000 cycles with maintenance, 10,000 without; electrical durability is 5,000 cycles at rated voltage. That's a long-life breaker for a main feeder that sees few operations per year.

MPN
EVS40H3NF20