Skip to main content
Schneider Electric EZC100N1060

Schneider Electric EZC100N1060 EasyPact EZC100N, 60 A, 1P, 2

MPN EZC100N1060
Obsolete

Schneider Electric EasyPact EZC100N, EZC100N1060, 1-pole circuit breaker, 60 A, TM-D thermal-magnetic trip, 25 kA Icu at 240 V AC, 18 kA at 240 V, 5 kA at 125 V DC.

$39.96 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZC100N1060 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeCircuit breaker
Voltage125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 18 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP20
Terminal pitch25 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-35 °C

All specifications

EZC100N1060 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-35...85 °C
Pollution degree3 conforming to IEC 60664-1 3 conforming to IEC 947-1
Depth60 mm
Width25 mm
Height130 mm
Mechanical life cycles13000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric EZC100N1060 is a 1-pole EasyPact EZC100N circuit breaker rated 60 A at 40 °C, with a TM-D thermal-magnetic trip unit. It carries a 25 kA Icu breaking capacity at 110–130 V AC, 18 kA at 220–240 V AC, and 5 kA at 125 V DC — all per IEC 60947-2. The 60 A frame and 25 mm width make it a compact fit for distribution panels where single-pole branch protection is needed.

At 240 V AC it clears 18 kA; at 400–415 V AC the Icu drops to 2.5 kA. For a 1-pole device on a 60 A frame, the 25 kA at 110–130 V AC is the headline number — that's the rating that governs selectivity with an upstream 25 kA or higher device. The 5 kA at 125 V DC matters for telecom or solar combiner boxes where a single pole switches DC.

The 25 mm width (one modular unit) snaps into a standard DIN-rail enclosure. IK07 impact rating handles accidental tool drops during commissioning.

Protection and ratings

Thermal-magnetic TM-D trip unit provides overload and short-circuit protection. Rated insulation voltage 690 V AC; operational voltage 415 V AC or 125 V DC. Mechanical durability 13,000 cycles — adequate for panel-switch duty, not for frequent motor starting.

MPN