Skip to main content
Schneider Electric LUCA1XBTQ

Schneider Electric LUCA1XBTQ TeSys U Standard Control Unit,

MPN LUCA1XBTQ
Obsolete

Schneider Electric TeSys U standard control unit, LUCA1XBTQ, 24 V AC control circuit, 0.25 kW at 400...440 V AC, plug-in front face.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LUCA1XBTQ specifications
ParameterValue
Main product or component typeStandard control unit
Voltage690 V AC
Coil voltage24 V AC
Utilization categoryAC-44 AC-41 AC-43
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Depth60 mm
Width45 mm
Height66 mm
ApplicationMotor control Motor protection
Fixing modePlug-in (front face)
Operating temperature-25...70 °C

Product details

What this control unit does in a TeSys U starter

The LUCA1XBTQ is a standard control unit for the TeSys U motor-starter system. It handles basic protection requirements: overload, short-circuit, phase failure, phase imbalance, and earth fault. The 24 V AC control circuit draws 70 mA sealed (90 mA with larger LUB power bases) and opens the power poles in 35 ms. That 35 ms opening time means the starter clears a fault fast enough to limit let-through energy on a 0.25 kW motor at 400 V — the typical rating here.

The unit plugs into the front face of a TeSys U power base (LUB12, LUB32, or LUB38). No DIN-rail space consumed beyond the base itself. Dimensions are 45 mm wide, 66 mm high, 60 mm deep — the depth is the projection from the power-base face, so plan for 60 mm clearance in front of the DIN rail. IP20 on the front panel and wired terminals; IP40 outside the connection zone.

Rated for AC-44, AC-41, and AC-43 utilisation categories per IEC 60947-6-2. AC-44 is the toughest — switching motors with frequent inching and plugging. The tripping threshold is 14.2 x Ir ±20%, which means the magnetic short-circuit release picks up at roughly 14 times the set overload current.

Compliance and environmental tolerance

Certified to EN/IEC 60947-6-2, UL 60947-4-1, and CSA C22.2 No 60947-4-1 (with phase barrier). Rated insulation voltage 690 V (IEC) / 600 V (UL/CSA). Safe separation of control and main circuits at 400 V SELV. Fire resistance of 960 °C on live-part supports, 650 °C elsewhere. TH protective treatment per IEC 60068 for tropical environments. Immunity to microbreaks up to 3 ms and voltage dips down to 70% for 500 ms — keeps the starter online through brief line disturbances.

MPN