Schneider Electric LV848185

Schneider Electric LV848185 MasterPact MTZ2 1250 A Circuit B

MPN LV848185
Active

Schneider Electric MasterPact MTZ2, fixed circuit breaker, 4P, 1250 A at 40 °C, H1 66 kA at 415 V AC, Category B selectivity, IP30.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848185 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch115 mm
Connection surface topFront Rear
Connection surface bottomFront Rear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C

All specifications

LV848185 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Depth300 mm
Width537 mm
Height352 mm
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ2 fixed breaker — 1250 A, 66 kA, Category B

The LV848185 is a fixed-mount MasterPact MTZ2 circuit breaker from Schneider Electric, rated 1250 A at 40 °C with H1 performance level delivering 66 kA Ics across the full voltage range up to 690 V AC. Four poles, Category B selectivity — meaning it holds full rated short-time withstand (66 kA for 1 s) so downstream faults are cleared without tripping this main breaker, provided the coordination study respects the Icw envelope.

Selectivity and coordination — what the 66 kA Ics and Category B mean for the panel

Category B per IEC 60947-2 means this breaker is designed for selective coordination: it carries a rated short-time withstand current (Icw) of 66 kA for 0.5 s and 1 s, and 36 kA for 3 s. That Icw window lets downstream protective devices clear a fault before this main breaker trips — critical for a main or tie breaker in a switchboard where nuisance tripping takes the whole bus off-line.

Mounting and integration — fixed-mount, 4P, front/rear connections

Fixed-mount design, 537 mm wide × 352 mm high × 300 mm deep. Mounting support is rails or a base plate — the chassis bolts into the switchgear cubicle, not a DIN rail. Both upside and downside connections accept front or rear terminations, so the same breaker works in either cable-entry or busbar-drop configurations. Connection pitch is 115 mm, which matches standard MasterPact MTZ2 busbar riser spacing. Neutral is on the right side of the 4-pole assembly.

Environmental and endurance limits

Altitude derating applies above 2000 m — no derating needed up to 2000 m, above that consult the thermal curve. Electrical durability is 10,000 cycles at 440 V and 690 V AC per IEC 60947-2, with AC-3 motor-switching duty rated at 6000 cycles. Mechanical durability is 25,000 cycles with periodic preventive maintenance. Power dissipation at rated current is 100 W — factor that into the cubicle ventilation calculation if the breaker is in a sealed compartment with other heat sources.