Skip to main content
Schneider Electric LV848356

Schneider Electric LV848356 MasterPact MTZ3 5000 A Drawout C

MPN LV848356
Active

Schneider Electric MasterPacT MTZ3, LV848356, drawout circuit breaker, 4P, 5000 A at 40 °C, H2 performance 150 kA 415 V AC, Category B, rear connection.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

LV848356 specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui1000 V AC 50/60 Hz
IP ratingIP30
Terminal pitch230 mm
Connection surface topRear
Connection surface bottomRear
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degree3 conforming to IEC 60947-1
Mechanical life cycles10000 cycles with periodic preventive maintenance
ApplicationPower distribution protection
Operating temperature-25...70 °C

Product details

MasterPact MTZ3 — 5000 A drawout breaker for main distribution

The Schneider Electric LV848356 is a MasterPact MTZ3 drawout circuit breaker rated 5000 A at 40 °C, 4-pole, with H2 performance class delivering 150 kA Ics at 415 V AC. It is designed for power distribution protection in main switchboards and industrial feeders where Category B selectivity is required — meaning it coordinates with downstream breakers to isolate only the faulted branch, keeping the rest of the plant online. The short-time withstand current (Icw) is 100 kA for up to 3 seconds, giving protection engineers headroom for selective coordination studies. Maximum breaking time is 25 ms, closing response within 80 ms.

At 690 V AC the Ics is 100 kA. Category B selectivity (per IEC 60947-2) means the breaker has a deliberate short-time delay, allowing downstream devices to clear first; this is essential for main-tie-main or feeder configurations where nuisance tripping of the entire plant is unacceptable. The Icw of 100 kA for 3 seconds gives the protection engineer a wide window to set time-current curves. Compare this to a standard Category A breaker that typically holds Icw for only 1 second — the MTZ3's 3-second rating simplifies coordination with downstream MCCBs and fuses.

Integration — drawout mounting, rear connection, panel dimensions

Drawout mounting means the breaker chassis stays wired in the switchboard while the removable portion can be racked out for maintenance or replacement without disturbing power connections. The breaker mounts on rails or a base plate. Both upside and downside connections are rear, which is typical for main switchboard feeders where busbars run behind the breaker. Overall dimensions with chassis: 403 mm depth, 1016 mm width, 479 mm height. Without chassis: 300 mm depth, 838 mm width, 300 mm height. IP30 protection is suitable for indoor switchboard installation; pollution degree 3 per IEC 60947-1 means the environment has conductive pollution (typical of industrial switchrooms).

Electrical durability: 6000 cycles under AC-3 duty (motor switching) at 440/690 V, and 1500 cycles under AC-23A (occasional switching of motors or other inductive loads). Mechanical durability is 10,000 cycles with periodic preventive maintenance. Power dissipation at rated current is 670 W — factor this into switchboard ventilation calculations. Neutral position is right. Sensor rating options span 2500 A to 5000 A, allowing the same frame to be used with lower-rated sensors for feeder applications.

MPN
LV848356