Skip to main content
Schneider Electric MGN60515

MGN60515 C60N MCB, 32 A, D Curve, 10 kA, 1P

MPN MGN60515
Obsolete

Schneider Electric, Multi9 series, C60N miniature circuit breaker, MGN60515, 32 A rated current, D curve, 10 kA breaking capacity, 1 pole, DIN rail mount.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

MGN60515 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage240 V AC 50/60 Hz phase to neutral
Utilization categoryCategory A conforming to EN/IEC 60947-2
IP ratingIP20
Temp storage max80 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-30 °C
Storage temperature-40...80 °C
Pollution degree3 conforming to EN/IEC 60947-2

All specifications

MGN60515 additional specifications
ParameterValue
Depth73 mm
Width18 mm
Height81 mm
Electrical life cycles10000 cycles conforming to EN/IEC 60947-2
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-30...70 °C

Product details

It's a single-pole thermal-magnetic breaker rated 32 A at 50 °C per EN/IEC 60947-2, with a D trip curve — meaning its magnetic trip threshold is 12 x In (±20 %), so it handles high inrush currents from motor or transformer loads without nuisance tripping.

Breaking capacity: 10 kA Icu at 240 V AC phase-to-neutral, and 3 kA Icu at 415 V AC phase-to-neutral, both per EN/IEC 60947-2. The service breaking capacity (Ics) is 75 % of those values — 7.5 kA at 240 V, 2.25 kA at 415 V. The IP20 finger-safe terminals are fine for enclosed panels; don't use it in a wet location without an outer enclosure. The toggle gives clear ON/OFF indication and a contact position indicator confirms the state even if the toggle is forced.

Snaps onto 35 mm symmetrical DIN rail. Occupies 2 x 9 mm pitches (18 mm wide) — one standard module width for a single-pole breaker. Height 81 mm, depth 73 mm. Tunnel terminals accept 1.5 to 35 mm² rigid or flexible (with or without ferrule); strip length 14 mm, torque to 3.5 N·m. That's a solid grip for a 32 A circuit.

MPN
MGN60515