ABB 3ABD00035958-D — AC Drive (VFD) 480V

ABB 3ABD00035958-D ACS880-01 Drive, 0.75 kW, 2.4 A, Frame R1

MPN3ABD00035958-D
Active

ABB ACS880-01 series, LV AC industrial wall-mounted single drive, 3ABD00035958-D, 0.75 kW, 2.4 A, Frame Size R1, 380-415 V 3-phase, IP21.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

3ABD00035958-D — Power & Output
ParameterValue
Output power, normal duty0.75 kW
Output current, normal duty2.4 A
Output power, heavy duty0.55 kW
Output current, heavy duty1.8 A
Output power, light overload0.75 kW
Output current, light overload2.3 A
Efficiency class (IE)IE2
3ABD00035958-D — Input / Supply
ParameterValue
Input voltage range380 ... 415 V
Number of phases3-phase
Frequency47.5 ... 63 Hz
3ABD00035958-D — Mechanical & Cooling
ParameterValue
Frame sizeR1
NEMA enclosure typeType1
Degree of protection (IP)IP21
Mounting typeWall-mounted

Product details

The ABB 3ABD00035958-D is a wall-mounted single drive rated 0.75 kW normal-use output at 2.4 A, fed from a 380–415 V three-phase supply. Frame R1 fits a wall-mount gland plate without needing floor space. Efficiency lands at IE2, which meets the baseline for most industrial installations in regions where IE3 isn't mandated for this power band. The IP21 enclosure and NEMA Type 1 rating mean it's suited for clean indoor environments — no washdown, no dust loads.

Normal-use output is 0.75 kW at 2.4 A — that's the continuous rating for a typical variable-torque load like a fan or pump. Light-overload use is spec'd at 0.75 kW at 2.3 A, a slight current reduction from normal duty that buys headroom for occasional peak demands. For a sourcing decision: if the motor nameplate says 0.75 kW and the application is a centrifugal pump, the normal-duty line fits. If it's a conveyor with breakaway torque, size against the heavy-duty column.

Frequently asked questions

What is 3ABD00035958-D's listed frame size?

Frame size is R1, which is the smallest mechanical format in the ACS880-01 wall-mounted range.

What are the normal-duty and heavy-duty output ratings?

Normal-duty output is 0.75 kW at 2.4 A. Heavy-duty output is 0.55 kW at 1.8 A. Light-overload output is 0.75 kW at 2.3 A.

What is the enclosure protection rating?

IP21 with NEMA Type 1 enclosure, suitable for clean indoor environments without washdown or dust exposure.

MPN